POWERWARE
®
9120
700, 1000, 1500, 2000 & 3000VA
User’s Guide
Important Notice
The UPS ground (earth) conductor carries leakage current from the loads in addition to
any leakage current generated by the UPS. This UPS generates no more than 1 mA of
current. To limit the total leakage current to 3.5 mA, the load leakage must be limited to
2.5 mA. The three-wire receptacle that you plug the UPS into must have a good (low-
impedance) ground (protective earth) connection to provide a safe path for leakage cur-
rent.
OMM91203kRev1.qxd
© Copyright 2007, Eaton Powerware. All rights reserved.