Operation
Eaton 9135 5000/6000 VA UPS User’s Guide 164201726—Rev 4
www.eaton.com/powerquality
36
Table 9 displays the maintenance options.
Life Cycle Monitoring
Life Cycle Monitoring (LCM) displays messages on the UPS front panel and through the communication
channels, at every important stage of the UPS’s life. Press the
button to display LCM warning details.
Figure 30.
LCM W
arning Screen
Anticipate Maintenance
Automatic warnings appear when maintenance actions need to be planned (see Table 10).
Table 9. Maintenance Settings
Function
Sub-Function
Option/Display
Comments
Model
Power Module
SN: xxxxxxxxx
SOFT: xxx
Serial number
Soft version
Frame
Alarm History
Read
Description
Date Hour
Alarm xxx
10 alarms can be stored automatically
Erase
No / Yes
Manual Batt Test
Manual Battery Test
No / Yes
Led & Buzzer Test
Led & Buzzer Test
No / Yes
Life Cycle Monitoring
LCM
Enable / Disable
Life cycling monitoring alarms
Statistics
Auto Statistics
Statistics
Custom Statistics
Reset Date ?
Are you sure ?
Table 10. LCM Warning Details
LCM Warning Details
Signification
BATTERY CHECK RECOMMENDED
Battery is approaching its reliability end of life. Risk to reduce dramatically
backup time.
(