Troubleshooting
Eaton 9135 5000/6000 VA UPS User’s Guide 164201726—Rev 4
www.eaton.com/powerquality
47
Table 18. Messages for Troubleshooting Not Requiring Eaton Service
Troubleshooting Requiring Eaton Service
Figure 38. Troubleshooting LED
NOTE
Press the
button to display the details described in Table 18.
Displayed Details
Problem
Correction
NO BATTERY
The battery is incorrectly connected.
Check battery connections.
I/O BAD CONNECTION
Utility input is not connected to the correct
terminals.
Check AC wiring.
NO POWER MODULE
The power module is not inserted.
Check power module connections (see page 43).
NO BATTERY MODULE
The battery tray is incorrectly connected.
Check battery connections (see page 43).
INV THERM OVERLOAD
The
UPS
shuts down automatically because of a
major overload.
Check the power drawn by the connected devices
and disconnect any non-priority devices.
INVERT LIMITATION
Short circuit conditions on output devices.
Check the installation at the
UPS
output (wiring,
fault equipment).
(
NOTE
In case of multiple fault, press the
button and the button to get access to
further details (see Table 19).
(
Escape
Up
Down