INSTALLATION
Eaton
®
9140 (9910-E82/E83) UPS Installation Guide for IBM
®
Applications
S
164201715 Rev 2
www.eaton.com/ibm
17
Rack Setup for the UPS
C
A
U
T
I
O
N
The UPS is heavy (42 kg/92 lb). A minimum of two people are required to remove the UPS
from its carton.
NOTE
Mounting rails are required for each individual cabinet.
NOTE
The recommended configuration is to install the optional EBM(s) in the lower part of
the rack, with the UPS directly above the EBM(s).
To install the UPS rail kit:
1.
Select the proper holes in the rack for positioning the UPS in the
rack (see Figure 13).
NOTE
The UPS takes up position 1 through position 18.
Position 2
Position 5
Position 8
Position 17
Screw Positions for
Rail and Lower Front
Mounting Bracket
Screw Positions for
Upper Front
Mounting Bracket
Position 11
Position 4
Position 3
Bottom of Rack or
Top of Other Cabinet
Figure 13. Front Rail Screw Positions for the UPS