OPERATION
Eaton
®
9140 (9910-E82/E83) UPS Installation Guide for IBM
®
Applications
S
164201715 Rev 2
www.eaton.com/ibm
45
Table 10. User Settings (continued)
Default Setting
Available Settings
Description
Language
Select Language: <English> <Spanish>
<French> <German> <Finnish>
English
XCP Load Control
[Enabled][Disabled]
Enabled
Upper Bypass V
+0 t20% (1% increments)
+20%
Lower Bypass V
-0 through -20% (1% increments)
-20%
Bypass Freq Dev
(Bypass Frequency Deviation Limits)
1 through 5 Hz (1 Hz increments)
NOTE This value sets the limits from 1 Hz to
5 Hz of the nominal output configuration.
3 Hz
Qualify Bypass
[Enabled][Disabled]
NOTE This setting enables or disables the
bypass qualification rules. When set to
Disabled, Bypass is always available.
Enabled
Allow Bypass
[Enabled][Disabled]
Enabled
Set Baud Rate
Port 1 (RS232): [19200] [9600] [2400] [1200]
Port 2 (SERVICE): [19200] [9600] [2400] [1200]
9600
Set Site (Wiring) Fault
[Enabled][Disabled]
Disabled
Contact Config*
Contact Usage: [REPO][ROO][Disabled]
Contact Type: [N/O][N/C]
REPO
N/O
Frequency Converter Mode
[Enabled][Disabled]
NOTE If bypass input fails while operating on
second feeder input and neither utility
frequency nor bypass frequency is available
to sync with, the UPS operates with different
frequencies for output and input. When this
setting is Enabled, the UPS operates at a 50%
derating to continue to meet operating
specifications. When set to to Disabled, the
UPS operates with no load derating.
Enabled
* Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise,
the changes do not take effect.