INSTALLATION
Eaton
®
9140 (9910-E82/E83) UPS Installation Guide for IBM
®
Applications
S
164201715 Rev 2
www.eaton.com/ibm
24
NOTE
To install the optional seismic mounting brackets, the length of the rails must be
between 72 and 81 cm (28.5 and 32 inches).
16.
If installing the optional seismic mounting brackets, align the two
UPS seismic mounting brackets with the screw holes on the sides
of the UPS above the rear mounting brackets. Loosely secure the
brackets with the eight supplied wing bolts. See Figure 21.
Do not tighten the wing bolts.
Figure 21. Installing the Optional UPS Seismic Mounting Brackets