Installation
10
Eaton Bypass Power Module (BPM) User’s Guide P-164000628—Rev 2
www.eaton.com/powerquality
5.
To wire the BPM, see “Signal Wire Routing” on page 11.
6.
After wiring is complete, replace the cover removed in Step 3.
30A Wallmount Linecord BPM Installation
CAUTION
l
The BPM distributes high density power in a small form factor.
l
Read the complete installation procedure before beginning any electrical wiring.
To install the BPM in a wallmount form factor:
1.
Select a mounting location for the bypass switch within sight of the UPS.
2.
Use the provided wallmount brackets to firmly secure the BPM to the wall (Figure 14).
Figure 14. BPM with Wallmount Brackets
3.
Use the provided wallmount brackets to firmly secure the BPM to the wall.
4.
Remove the six (6) screws on the BPM front cover and remove the cover.
Remove any packing material inside the BPM.
5.
Remove the knockouts in the bottom of the BPM as needed for wiring.
6.
To wire the BPM, see “Signal Wire Routing” on page 11.
7.
After wiring is complete, replace the cover removed in Step 4.
NOTE
The bypass switch should be mounted securely to a sturdy surface. You may need
to turn the cabinet 90 degrees (on its side) to enable operator access to the switch
handle.
Summary of Contents for Powerware 9155
Page 27: ......
Page 28: ...P 164000628 2 P 164000628 2...