9x55 8–15 kVA Battery Upgrade (8–15 kVA)
—Rev 1
15
15. Connect the newly provided adapter harness (see
Figure 16
) to the UPS battery tray wiring, using the
crimp tool (or equivalent) illustrated in
Figure 17
. It is recommended that
crimp tool PN 59824-1
or
equivalent is used in this step. Ensure that the two pieces of black heat shrink (highlighted in yellow in
Figure 18
) are on the adapter assembly. Then insert the negative (black) wire into the crimp terminal on the
black wire of the retrofit adapter (see
Figure 18
).
Figure 16. New Adapter
Figure 17. Recommended Crimp Tool
WARNING
Ensure that no bare wire is exposed outside of the crimp terminal.
Battery Upgrade Procedure