background image

UPS WITH BYPASS ELECTRICAL INSTALLATION

Eaton 9170

+

 UPS (3–18 kVA) User's Guide  

S

  164201393 Rev E

 www.eaton.com/powerquality

33

14.

If any external hardwired control signals are required (EPO or
Generator On), connect the wiring as shown in Figure 21.

C

 

A

 

U

 

T

 

I

 

O

 

N

EPO and external bypass circuits are not isolated from line voltage, and wiring must be
installed according to local codes using conduit or suitable primary supply cables.

The Generator On signal is isolated from line voltage and can be
treated as NEC Class 2 wiring.

Use 14–20 AWG, 600V wire (UL) or 14–26 AWG, 300V wire (CSA)
for all input control signals.

Generator On
(normally open)

Signal
Common

Emergency Power-off (normally closed)

External Bypass *(short to common when active)

Generator Set

Plastic Cable Tie

Figure 21. Input Control Signal Wiring (for External Controls)

15.

Place the signal wires through the proper conduit or grommet
above the terminal block and attach to appropriate terminals.
Secure each connection by torquing terminal screws to a maximum
0.4 Nm (3.5 lb in). Provide strain relief for cables by installing plastic
cable ties.

NOTE  

Do not strain relieve EPO or external bypass wiring with the same cable tie used for

Generator On wires.

16.

Remove the jumper between terminals 5 and 6 only if you are
wiring from an EPO switch. (See “Changing Parameter Settings”
on page 83 for information about accessing menu 4 3 2 to view or
change the EPO switch type.)

17.

When all connections have been made and checked, reinstall the
bypass switch front cover and UPS cabinet rear covers using the
original screws.

Summary of Contents for Powerware 9170+ UPS 3-18 kVA

Page 1: ...Powerware Series Eaton 9170 UPS 3 18 kVA User s Guide...

Page 2: ...he EC Declaration of Conformity is available upon request for products with a CE mark For copies of the EC Declaration of Conformity contact Eaton Corporation Koskelontie 13 FIN 02920 Espoo Finland Ph...

Page 3: ...esidential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense ICES 003 This Class A Interference Causing Equipment meet...

Page 4: ...onal information such as important operating and maintenance instructions This symbol indicates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead...

Page 5: ...tion Three and Six Slot Cabinets 14 Floor Anchor Kit Installation 16 Moving the Cabinets 17 3 UPS with Bypass Electrical Installation 19 Input Current Ratings 21 Bypass Switches 22 Bypass Switch Opera...

Page 6: ...nu Map 87 9 Communication 89 Power Management and Protection Software 89 Optional Interface Kits 89 Communication Slots 89 ConnectUPSt Web SNMP Card BD Model 90 Relay Interface Card BestDock Model 90...

Page 7: ...in power modules and automatically transfers control and load to the remaining power modules All power modules share the load requirements equally For example three power modules are capable of suppl...

Page 8: ...a single output voltage 200 208 220 230 or 240 Vac DO NOT mix the two types of power modules in the same Eaton 9170 cabinet S Do NOT install more than seven power and or optional battery charger modu...

Page 9: ...ension de sortie 200 208 220 230 ou 240 Vca NE m langez PAS les deux types de blocs de puissance dans le m me module d unit d alimentation S N installez PAS plus de sept chargeurs de batteries optionn...

Page 10: ...m dulos de potencia en el mismo gabinete de la Unidad de distribuci n de alimentaci n S NO instale en los m dulos de potencia del sistema m s de siete m dulos de potencia y o de cargadores opcionales...

Page 11: ...the 3 slot and 9 slot configurations and identify basic Eaton 9170 system features Six slot and 12 slot cabinets are also available external battery cabinets are available in 6 9 and 12 slot sizes Fro...

Page 12: ...INTRODUCTION Eaton 9170 UPS 3 18 kVA User s Guide S 164201393 Rev E www eaton com powerquality 6 Front Panel Display Front Cover Cabinet Base Figure 3 Nine Slot Cabinet Front View...

Page 13: ...Slots Power Outlets optional Input Power Cable optional DB 9 Communication Port Wiring Access Figure 4 Nine Slot Cabinet Rear View Handle Latch Release Insertion Extraction Cams Handle Thumbscrew Fig...

Page 14: ...INTRODUCTION Eaton 9170 UPS 3 18 kVA User s Guide S 164201393 Rev E www eaton com powerquality 8...

Page 15: ...sizes require the following clearances to allow for servicing and adequate ventilation S Sides 15 2 cm 6 S Top and back 30 5 cm 12 S Front 91 5 cm 36 If flexible conduit connects the UPS to the servic...

Page 16: ...s are shipped on one pallet Refer to the unpacking instruction sheet LTS 1724 packed inside the UPS shipping carton NOTE Verify that all Eaton 9170 UPS power modules are the proper type for the UPS ca...

Page 17: ...ets 1 Lower the four cabinet casters one at each corner of the cabinet base by using a 1 2 hex style socket wrench to turn each bolt clockwise 2 With all casters fully extended carefully roll the cabi...

Page 18: ...ired units continue to UPS with Bypass Electrical Installation on page 19 or UPS Electrical Installation on page 39 Caster Cart Installation Three and Six Slot Cabinets An optional caster cart ASY 052...

Page 19: ...racket Installation Twelve Slot Cabinet Only The 12 slot Eaton 9170 UPS cabinet is shipped with two stabilizer brackets These brackets must be attached to the wall or the floor behind the UPS cabinet...

Page 20: ...re requires two people to lift and position the cabinet into the equipment rack Install the cabinet in the rack before installing power and battery modules and before making connections to the intende...

Page 21: ...front of the UPS cabinet see Figure 9 Tab Slots Metal Clip Nuts Figure 9 Metal Clip Nut and Tab Slot Locations 5 Install a rack mount ear two for 6 slot cabinets on each side of the UPS cabinet see Fi...

Page 22: ...r anchor kit ASY 0548 is available for all sizes of the Eaton 9170 UPS The kit helps to stabilize the UPS or battery cabinet in the event of accidental bumps or small floor movements Any testing to sp...

Page 23: ...the cabinet Caster Cart Installation Three and Six Slot Cabinets on page 12 describes how to set the four foot pads on this cart to keep the cabinet from rolling when properly positioned The 9 and 12...

Page 24: ...ing the cabinet to its intended position turn all four caster bolts counter clockwise until the cabinet rests on the floor Place a plastic cap into each bolt access hole NOTE If the floor is uneven an...

Page 25: ...uch as a licensed electrician should perform the electrical installation Risk of electrical shock The Eaton 9170 UPS input power may be hardwired through conduit to either a main power source circuit...

Page 26: ...201393 Rev E www eaton com powerquality 20 External Bypass Switch Off Service Line Off Service Line UPS UPS Off Service Line UPS User Supplied if required External Batteries optional Building Service...

Page 27: ...40 Vac 50 60 Hz UPS Capacity Input Circuit Breaker Rating 3 kVA 25A 6 kVA 40A 9 kVA 60A 12 kVA 80A 15 kVA 100A 18 kVA 125A NOTE If you are installing an optional battery charger module refer to that u...

Page 28: ...ies given in Table 310 16 of the National Electrical Code ANSI NFPA 70 1999 and article 220 All circuit conductors including the neutral conductor must be the same size ampacity wire Code may require...

Page 29: ...cts the load directly to AC input power and disconnects UPS output However because SERVICE also disconnects AC input from the UPS this is the appropriate position for UPS maintenance or repair Bypass...

Page 30: ...e numbers on page NO TAG and ask for a UPS technical representative 1 Press the menu button on the front panel display see Figure 54 on page 80 The System Status Menu displays 2 Press the B button unt...

Page 31: ...th Depth Mounting Centers A B C D E BPE12BBM1A BPE12MBB1A 40A 300 Vac CSA 50A 300 Vac UL T V 53 4 cm 21 0 35 6 cm 14 0 17 2 cm 6 8 28 0 cm 11 0 50 8 cm 20 0 12 3 kg 27 lb BPE14BBM1A BPE14MBB1A 80A 300...

Page 32: ...bypass switch should be mounted securely to a sturdy surface You may need to turn the cabinet 90 degrees on its side to enable operator access to the switch handle 2 Remove the six screws in the bypas...

Page 33: ...com powerquality 27 Entrance Panel Battery Cable Wiring Access Hole for Optional EPO and Bypass Input Signals Wiring Access Hole for an Optional Generator Input Signal Figure 14 UPS Power Entrance Pan...

Page 34: ...AC output conductors must be run through separate conduits UPS output circuits must be installed in dedicated conduit systems and not shared with other electrical circuits Figure 15 shows input and o...

Page 35: ...ess cover and the proper installation wiring diagram make the terminal strip connections and tighten all connections as specified in Table 2 on page 22 Use copper wire that is the appropriate size for...

Page 36: ...N Confirm that the UPS is wired for the proper input voltage as shown in Figure 17 and that the proper power modules either split phase or universal are installed to produce the desired output voltage...

Page 37: ...pacity of the UPS has not been reached N DC 50 or 60 Hz 100 200 110 220 127 220 120 208 or 120 240V Out Menu 4 2 4 set to 200 220 208 or 240 as required X2 X1 X X N L1 X L2 100 110 127 or 120 50 200 2...

Page 38: ...pair of wires in this cable CAUTION EPO and external bypass circuits are not isolated from line voltage and wiring must be installed according to local codes using conduit or suitable primary supply...

Page 39: ...d External Bypass short to common when active Generator Set Plastic Cable Tie Figure 21 Input Control Signal Wiring for External Controls 15 Place the signal wires through the proper conduit or gromme...

Page 40: ...t Voltage UPS Output Voltage Output Wires Wiring Diagrams Input Output System 100 200 110 220 120 208 120 240 127 220 100 200 110 220 120 208 120 240 127 220 L1 L2 N Figure 17a on page 30 Figure 18 on...

Page 41: ...conductors All AC circuit conductors including the neutral conductor must be the same size ampacity have the same rating 75 C copper wire and be sized according to the input circuit breaker See Table...

Page 42: ...uality 36 S 110 220 Input 110 220 Output S 120 208 Input 120 208 Output S 120 240 Input 120 240 Output S 100 200 Input 100 200 Output S 127 220 Input 127 220 Output 3 2 3 2 3 3 7 4 5 7 6 1 Figure 22 E...

Page 43: ...E www eaton com powerquality 37 2 S 200 Input 200 Output S 208 Input 208 Output S 220 Input 220 Output S 230 Input 230 Output S 240 Input 240 Output 1 3 2 3 3 3 7 4 5 7 6 Figure 23 External Bypass Swi...

Page 44: ...Guide S 164201393 Rev E www eaton com powerquality 38 S 220 Input 220 Output S 230 Input 230 Output S 240 Input 240 Output 2 1 3 2 3 3 3 7 4 5 7 6 Figure 24 External Bypass Switch L1 N Universal Powe...

Page 45: ...installation Risk of electrical shock If a bypass switch is not used the UPS input may be hardwired through conduit to a main power source circuit breaker and the UPS output may either be hardwired to...

Page 46: ...reaker Sizes 200 240 Vac 50 60 Hz UPS Capacity Input Circuit Breaker Rating 3 kVA 25A 6 kVA 40A 9 kVA 60A 12 kVA 80A 15 kVA 100A 18 kVA 125A NOTE If you are installing an optional battery charger modu...

Page 47: ...n FOR U S INSTALLATIONS READ THIS IMPORTANT NOTE This table lists the mm2 and AWG wire size for each circuit breaker size shown on the wiring diagrams The minimum recommended circuit breaker sizes for...

Page 48: ...To install the UPS without an external bypass switch 1 Unscrew and remove the rear cover s of the UPS top cover on 3 or 6 slot top two covers on 9 or 12 slot See Figure 26 The entrance panel contains...

Page 49: ...eaton com powerquality 43 Entrance Panel Battery Cable Wiring Access Hole for Optional EPO Wiring Access Hole for an Optional Generator Input Signal Figure 26 UPS Power Entrance Panel Nine Slot Cabine...

Page 50: ...S output circuits must be installed in dedicated conduit systems and not shared with other electrical circuits Figure 27 shows input and output wiring terminals inside the Eaton 9170 UPS cabinet 3 2 1...

Page 51: ...AUTION Confirm that the UPS is wired for the proper input voltage as shown in Figure 28 and that the proper power modules either split phase or universal are installed to produce the desired output vo...

Page 52: ...an overload alarm even if the full capacity of the UPS has not been reached N DC 50 or 60 Hz 100 200 110 220 127 220 120 208 or 120 240V Out Menu 4 2 4 set to 200 220 208 or 240 as required X2 X1 X X...

Page 53: ...ignal Common Emergency Power off normally closed External Bypass short to common when active Generator Set Plastic Cable Tie Figure 31 Input Control Signal Wiring 9 Place the signal wires through the...

Page 54: ...Output Voltage Output Wires Wiring Diagrams Input Output System 100 200 110 220 120 208 120 240 127 220 100 200 110 220 120 208 120 240 127 220 L1 L2 N Figure 28a on page 45 Figure 29 on page 46 Figur...

Page 55: ...sized according to the input circuit breaker See Table 7 on page 41 for recommended wire sizes The UPS input and output conductors must be run through separate conduits NOTE 3 The customer must provid...

Page 56: ...uality 50 3 S 110 220 Input 110 220 Output S 120 208 Input 120 208 Output S 120 240 Input 120 240 Output S 100 200 Input 100 200 Output S 127 220 Input 127 220 Output 2 2 4 6 6 5 1 Figure 32 No Extern...

Page 57: ...E www eaton com powerquality 51 S 200 Input 200 Output S 208 Input 208 Output S 220 Input 220 Output S 230 Input 230 Output S 240 Input 240 Output 1 2 2 4 6 6 5 Figure 33 No External Bypass L1 L2 Uni...

Page 58: ...s Guide S 164201393 Rev E www eaton com powerquality 52 S 220 Input 220 Output S 230 Input 230 Output S 240 Input 240 Output 1 2 2 4 6 6 5 Figure 34 No External Bypass L1 N Universal Power Modules NOT...

Page 59: ...install more than seven power and or optional battery charger modules in the system NOTE In isolated output installations connect the UPS green and yellow neutral to ground wire N G bond to the UPS o...

Page 60: ...l to Ground Bonding for Isolated Output As required under safety regulations issued by various regulatory agencies the UPS cabinet must have a ground bond connection for the neutral terminal of an iso...

Page 61: ...the UPS rear cover are located directly below the line input terminals Figure 15 on page 28 shows input and output wiring terminals inside the Eaton 9170 UPS cabinet If there is any question as to th...

Page 62: ...rcuit conductors All AC circuit conductors including the neutral conductor must be the same size ampacity have the same rating 75 C copper wire and be sized according to the input circuit breaker See...

Page 63: ...t 100 200 Output S 120 208 Input 120 240 Output BBM bypass required S 110 220 Input 110 220 Output S 115 230 Input 115 230 Output S 120 240 Input 120 240 Output 1 4 2 4 2 3 4 4 9 5 7 9 6 8 Figure 38 E...

Page 64: ...58 S 100 200 Input 100 200 Output S 120 208 Input 120 240 Output S 110 220 Input 110 220 Output S 115 230 Input 115 230 Output S 120 240 Input 120 240 Output 1 4 3 4 7 9 9 6 8 Figure 39 No External By...

Page 65: ...require the bypass switch to be BBM contact your service representative for details S 120 208 Input 120 208 Output S 127 220 Input 127 220 Output 1 4 2 4 2 3 4 4 9 5 7 9 6 8 10 Figure 40 External Bypa...

Page 66: ...4201393 Rev E www eaton com powerquality 60 S 120 208 Input 120 208 Output S 127 220 Input 127 220 Output 1 4 3 4 7 9 8 9 6 10 Figure 41 No External Bypass L1 L2 N Isolated Output for Derived Three Ph...

Page 67: ...external battery cabinet verify that all AC input power is removed from the UPS Open the input service circuit breaker or turn the external bypass switch to the SERVICE position S Disconnect all batt...

Page 68: ...pair of pliers to bend the narrow links 1 and 2 in Figure 43 between the outer edge of the lower breakaway panel and the rear panel 4 Use the pliers to bend the entire breakaway panel at 3 and 4 in Fi...

Page 69: ...onto the DC and DC bolts as shown in Figure 44 Replace the compression lug onto the DC bolt of the bus bar extension assembly Secure the assembly by replacing the two nuts removed in Step 6 8 Use the...

Page 70: ...the strain relief clamp shown in Figure 45 Remove the clamp by loosening the star nut on the inside of the entry plate leaving the nut in place Replace the clamp with a panel to conduit feedthrough an...

Page 71: ...orque all three compression lugs to 8 5 9 6 Nm 75 85 lb in 18 If an additional battery cabinet will be connected to the first in a daisy chain configuration use another external battery cabinet cable...

Page 72: ...ide S 164201393 Rev E www eaton com powerquality 66 To UPS or Previous Battery Cabinet To Next Battery Cabinet Figure 47 Connecting Additional Battery Cabinets 20 Reinstall the remaining rear covers u...

Page 73: ...switch button on each battery cabinet or unplug all battery strings in each battery cabinet S To reduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled in...

Page 74: ...sert a power module Lower the front slightly and lift the rear edge over the safety stop on the center support rail Keep the module handle extended until the module is fully inserted see Figure 48 Rai...

Page 75: ...t all power modules are properly installed and latched into the UPS cabinet 4 If you are installing power management software connect your computer to the UPS communication port shown in Figure 49 usi...

Page 76: ...been reached For Eaton 9170 UPS models with low voltage output receptacles it is recommended to divide loads between upper and lower receptacles as equally as possible In some configurations each set...

Page 77: ...tion port shown in Figure 51 using the supplied communication cable DB 9 Connector for Computer Cable Figure 51 Communication Port 5 If your unit is wired to an external bypass switch you must perform...

Page 78: ...ccess the UPS On Off function through the front panel display NOTE If the UPS has been manually set to operate in Bypass or Battery mode change the System Control Mode Preference menu 4 1 selection to...

Page 79: ...itch to LINE Measure the voltage to the protected equipment at the load distribution panel and verify that it is correct 14 Switch the bypass switch to UPS and verify the voltage to the protected equi...

Page 80: ...ing the load See DB 9 Communication Port on page 92 for details 20 If there are receptacles on the UPS rear panel plug the equipment to be protected into the UPS output receptacles NOTE DO NOT protect...

Page 81: ...t press the button Set Time time 14 51 38 ESC 4 The output voltage is the most important operating parameter you must set as part of the initial configuration screens Select the desired UPS output vol...

Page 82: ...larm occurs This setting affects only the alarm the system continues to operate as an N X system even if this parameter is left at the default value of 0 Set Redundancy RSetting 0 ESC 7 To password pr...

Page 83: ...PS switches automatically to and from Battery mode with no interruption 0 ms transfer time as AC input power drops and returns Batteries are charged in this mode Battery mode produces power from the b...

Page 84: ...low battery alarm condition the UPS automatically recovers and if the Auto Restart parameter is enabled switches to Double Conversion mode Auto Restart is enabled as a factory default After a discharg...

Page 85: ...de selection is set to Battery The UPS can not go directly from Off to Battery Removing Input Power Always transfer the UPS to Off mode before removing input power The batteries will discharge if the...

Page 86: ...rm LED red Illuminates to signal that the unit has detected an alarm condition 3 Battery LED yellow Illuminates to signal that the unit is operating on battery power and producing output voltage 4 Lin...

Page 87: ...own for a specific power module 0 is defined as System for observing overall system operation One or two triangles at the right of the display indicate which arrow buttons are active for moving within...

Page 88: ...inets Md AUTO M4 B7 12 St ON LINE acvout 232 V Config OFF Menu Figure 56 Front Panel Display Normal Operation Operating parameters on the third line of the display vary depending on the operating mode...

Page 89: ...utes of inactivity the UPS automatically deletes any active password level and returns to the normal running display Changing Parameter Settings Changing an operating parameter is similar to setting i...

Page 90: ...and Y buttons to scroll up and down through the log entries Each entry shows the date and time the unit switched to battery operation in 24 hour format and the duration of battery operation in hours...

Page 91: ...format and the duration in hours and minutes A typical alarm log entry is shown in Figure 58 2 2 6 0 A 02 05 17 51 04 35 Low Battery Slot Top ESC Figure 58 Alarm Log Entry Figure 58 displays the sixt...

Page 92: ...modules decrease load or add power modules Incompatible Module A power module with incompatible firmware has been installed in the system contact your service representative Battery Test NOTE The batt...

Page 93: ...re 60 shows all the Eaton 9170 system parameters The menu structure has six primary level menus System Status Menu 1 through Service Menu 6 Each primary menu has secondary items numbered by their loca...

Page 94: ...2 13 Full Load P1 1 2 6 VAOut 1 2 14 Full Load P2 1 2 7 VAout P1 N 1 2 15 PowerFactor L1 1 2 8 VAout P2 N 1 2 16 PowerFactor L2 1 3 1 Battery Volts 1 3 2 Runtime 1 3 3 Seconds on Battery ESC 4 3 1 In...

Page 95: ...170 UPS ships with a CD containing several of the software products Visit www eaton com pq software for the latest updates to the products on the CD as well as any new power monitoring management and...

Page 96: ...allows UPS dependent computer systems to automatically shut down during extended power outages using the NetWatch client software provided on the Software Suite CD or Web site Relay Interface Card Bes...

Page 97: ...causes fewer recognized line faults during generator instability S Frequency Glitch Count This parameter increases the number of bad frequency cycles before the unit transfers to battery power allowin...

Page 98: ...AC input power is restored during the 120 second delay S The UPS output automatically restarts after the UPS determines the normal AC input power is stable S The shutdown and restart timing represent...

Page 99: ...ery cabinets do require some attention to assure continued reliable service Follow Eaton s recommended maintenance schedule which includes S Check operating environment for clean cool dry conditions S...

Page 100: ...rned without first signaling the UPS NOTE When the red button is released the UPS remains in its internal Bypass mode Return the UPS to Auto mode by selecting that mode on the front panel display See...

Page 101: ...ace the front cover s 8 If the batteries are not properly installed the Open Cell alarm activates Check the batteries in the slot indicated on the alarm screen Power Module Replacement The Eaton 9170...

Page 102: ...try Label the original module with masking tape or some other identifier Record the serial number of the replacement module for your warranty 5 Insert the replacement module by sliding it carefully in...

Page 103: ...ry operation outside this tolerance On battery 50 Hz or 60 Hz 0 1 Hz Regulation 3 load regulation under any line load or battery condition Voltage Waveform Sine wave 3 THD at rated linear loads comput...

Page 104: ...kBTU hr 0 6 5000 32A 30A 28A 25A 40A 570W 1 95 kBTU hr 1 6 5000 48A 30A 28A 25A 60A 860W 2 93 kBTU hr 0 9 7500 48A 45A 42A 37 5A 60A 860W 2 93 kBTU hr Nine and Twelve Slot Cabinet CAUTION Do NOT inst...

Page 105: ...A 60A 860W 2 93 kBTU hr 2 6 5000 64A 30A 28A 25A 80A 1145W 3 90 kBTU hr 3 6 5000 80A 30A 28A 25A 100A 1430W 4 88 kBTU hr 4 6 5000 96A 30A 28A 25A 125A 1720W 5 85 kBTU hr 5 6 5000 102A 30A 28A 25A 125A...

Page 106: ...0000 96A 60A 56A 50A 125A 1720W 5 85 kBTU hr 3 12 10000 102A 60A 56A 50A 125A 1995W 6 75 kBTU hr 0 15 12500 80A 75A 70A 62 5A 100A 1430W 4 88 kBTU hr 1 15 12500 96A 75A 70A 62 5A 125A 1720W 5 85 kBTU...

Page 107: ...44A 15 14 5 14 13 12 5A 60A 860W 2 93 kBTU hr 0 6 4200 28 27 26 25 24A 30 29 28 26 25A 40A 570W 1 95 kBTU hr 1 6 4200 44 43 42 41 40A 30 29 28 26 25A 60A 860W 2 93 kBTU hr 0 9 6300 42 40 5 39 37 5 36...

Page 108: ...A 570W 1 95 kBTU hr 1 6 4200 44 43 42 41 40A 30 29 28 26 25A 60A 860W 2 93 kBTU hr 2 6 4200 60 59 58 57 56A 30 29 28 26 25A 80A 1145W 3 90 kBTU hr 3 6 4200 76 75 74 73 72A 30 29 28 26 25A 100A 1430W 4...

Page 109: ...88 86 84 82 80A 60 58 56 52 50A 125A 1720W 5 85 kBTU hr 3 12 8400 102 102 100 98 96A 60 58 56 52 50A 125A 1995W 6 75 kBTU hr 0 15 10500 70 67 5 65 62 5 60A 75 72 5 70 65 62 5A 100A 1430W 4 88 kBTU hr...

Page 110: ...sive chemicals and other contaminants The Eaton 9170 UPS uses internal fans to circulate the air for cooling The air must be free to circulate around the UPS and battery cabinet s Do not operate the U...

Page 111: ...with caster cart 49 5 cm 19 5 43 cm 17 0 65 cm 25 5 35 kg 78 lb 6 slot 80 cm 31 5 43 cm 17 0 65 cm 25 5 47 kg 103 lb 6 slot with caster cart 84 5 cm 33 25 43 cm 17 0 65 cm 25 5 52 kg 115 lb 9 slot 119...

Page 112: ...SPECIFICATIONS Eaton 9170 UPS 3 18 kVA User s Guide S 164201393 Rev E www eaton com powerquality 106...

Page 113: ...rm the selection by pressing the button labeled Yes If On Off control is password protected enter the user password 0377 In the event of a front panel display failure you can turn the unit on or off u...

Page 114: ...ton beside the switch before turning the switch Set the UPS to turn on in High Efficiency mode Go to menu 4 1 Select the system mode desired at power on by pressing the or button When the display show...

Page 115: ...ESC Figure 61 Typical System Active Alarm Display Figure 62 shows a detailed alarm entry Some alarms provide additional information on the second line of the display to help identify the cause of the...

Page 116: ...high because of a charger problem battery problem or incorrect parameter setting Contact your service representative E Low AC Output The UPS has shut down because the AC output voltage is too low to...

Page 117: ...ctive module T Call Service Module Handle Open firmware versions 2 22 and later The UPS has detected an open power module handle Look for the slot number third line on display of the power module and...

Page 118: ...ntact your service representative M Check Battery Open Cell A battery pair of modules has failed an open cell test Look for the slot number third line on display of the failed modules Verify that both...

Page 119: ...Please have the following information ready when you call the Help Desk S Model number S Serial number S Version number if available S Date of failure or problem S Symptoms of failure or problem S Cus...

Page 120: ...TROUBLESHOOTING Eaton 9170 UPS 3 18 kVA User s Guide S 164201393 Rev E www eaton com powerquality 114...

Page 121: ...s determined by Company All Warranted Items returned to Company and all parts replace by Company shall become the property of Company Expenses for any labor to repair the Warranted Item beyond the ini...

Page 122: ...OMPANY DOES NOT WARRANT SOFTWARE INCLUDING SOFTWARE EMBEDDED IN PRODUCTS THAT IS NOT CREATED BY COMPANY WITHOUT LIMITING THE FOREGOING COMPANY SPECIFICALLY DOES NOT WARRANT SOFTWARE SUCH AS LINUX THAT...

Page 123: ...0 9135 9140 9150 9155 9170 and FERRUPS GUARANTOR The Guarantor for the load protection guaranty set forth herein is Eaton Corporation Corporation an Ohio Corporation company Company LIMITED GUARANTY T...

Page 124: ...THER THAN THE PRODUCTS INCLUDING LOSS OF PROFITS OR REVENUE LOSS OF USE OF PRODUCTS LOSS OF DATA COST OF CAPITAL CLAIMS OF CUSTOMERS OF THE END USER OR ANY SPECIAL INDIRECT INCIDENTAL OR CONSEQUENTIAL...

Reviews: