Table 15. Isolation
Models 0650C and 0660C Output
Neutral-to-Ground Bonding
±
3% load regulation (under any line, load, or battery condition)
Neutral is carried through from input to output; a separate neutral-to-ground
bond is not required.
Model 0650I, 0660I, and 0660J
Isolation, Including Output
Neutral-to-Ground Bonding
True, separately derived power source as defined by National Electrical Code
Article 250-5d, with output neutral bonded to ground. No direct connection
between input and output; neutral-to-ground bond is required; other local codes
may take precedence.
Table 16. Split-Phase Model Specifications (ASY-0673)
3 kVA, 2500 Watts
Voltage
Input Current*
Output Current
Input Service*
Heat Dissipation
Normal Mode
200
16A
15A
220
15A
14A
208
14A
14.5A
25A
285W (0 98 kBTU/h )
220
13A
14A
25A
285W (0.98 kBTU/hr)
230
14.5A
13A
240
14A
12.5A
6 kVA, 5000 Watts
Voltage
Input Current*
Output Current
Input Service*
Heat Dissipation
Normal Mode
200
32A
30A
220
30A
28A
208
28A
29A
40A
570W (1 95 kBTU/h )
220
26A
28A
40A
570W (1.95 kBTU/hr)
230
29A
26A
240
28A
25A
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant
power module.