SPECIFICATIONS
EATON
Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide
S
164201393 Rev C
www.powerware.com
105
Table 18. Environmental and Safety
Operating Temperature
0
°
C to 40
°
C (32
°
F to 104
°
F)
Optimal battery performance: 25
°
C (77
°
F)
Storage Temperature
UPS with battery modules: –20
°
C to +40
°
C (–4
°
F to 104
°
F)
UPS without batteries: –40
°
C to +60
°
C (–40
°
F to 140
°
F)
Relative Humidity
5–95% noncondensing
Operating Altitude
Up to 3,050 meters above sea level (10,000 ft)
The maximum operating ambient temperature decreases 1
°
C per 300m above 1525m
(2
°
F per 1000 ft above 5000 ft)
Non-Operating Altitude
Up to 12,200m above sea level (40,000 ft)
Ventilation
The air around the UPS must be clean and free of dust, corrosive chemicals, and other
contaminants. The Powerware 9170
+
UPS uses internal fans to circulate the air for
cooling. The air must be free to circulate around the UPS and battery cabinet(s). Do not
operate the UPS in a sealed room or container.
Audible Noise
Less than 53 dBA
Surge Suppression
ANSI C62.41 Category B (formerly IEEE 587); IEC 61000-4-5
Safety Conformance
CAN/CSA C22.2, No. 107.1; UL 1778;
EN 50091-1-1 and IEC 60950
Agency Markings
UL, cUL, TÜV, CE, C-Tick, BCIQ
EMC (Class A)
EN 50091-2, FCC Part 15, ICES-003, VCCI
Table 19. Battery
Configuration
(2) 60V, 7.2 Ah batteries per string
Voltage
120 Vdc
Type
Sealed, maintenance-free, valve-regulated, lead-acid
Charging
Recharge time: 4 hr after full-load resistive discharge; 8 hr after half-load resistive
discharge, using standard internal battery charger.
Optional battery chargers at higher current ratings will be available for future product
release.