UPS WITH BYPASS ELECTRICAL INSTALLATION
EATON
Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide
S
164201393 Rev C
www.powerware.com
23
NOTE
In the UPS or LINE position, AC input power is still connected to the input terminals
inside the UPS.
Table 3. Bypass Switch Positions
Switch Position
Description
LINE
Connects the load directly to AC input power and disconnects UPS output. AC input power is
still connected to the UPS input.
OFF
Disconnects the load from the UPS output power and AC input power, as well as AC input
power to the UPS input.
UPS
Connects the UPS output to the load.
SERVICE
Like the LINE position, SERVICE connects the load directly to AC input power and disconnects
UPS output. However, because SERVICE also disconnects AC input from the UPS, this is
the appropriate position for UPS maintenance or repair.
To disconnect AC input power during maintenance or service, turn the
bypass switch to the SERVICE position. For MBB switches, you must
press the red button beside the switch before you can change the
switch position.
Table 4 shows the bypass switch models available for the Powerware
9170
+
UPS.
Table 4. Bypass Switch Specifications
Bypass Switch Models
See Figure 14
BBM
MBB
Rating,
Continuous
Height
Width
Depth
Mounting Centers
Weight
BBM
MBB
Continuous
(A)
(B)
(C)
(D)
(E)
BPE12BBM1A
BPE12MBB1A
40A/300 Vac
(CSA)
50A/300 Vac
(UL,TÜV)
53.4 cm
(21.0
”
)
35.6 cm
(14.0
”
)
17.2 cm
(6.8
”
)
28.0 cm
(11.0
”
)
50.8 cm
(20.0
”
)
12.3 kg
(27 lb)
BPE14BBM1A
BPE14MBB1A
80A/300 Vac
53.4 cm
(21.0
”
)
35.6 cm
(14.0
”
)
17.2 cm
(6.8
”
)
28.0 cm
(11.0
”
)
50.8 cm
(20.0
”
)
14.1 kg
(31 lb)
BPE20BBM1A
BPE20MBB1A
125A/300 Vac
53.4 cm
(21.0
”
)
35.6 cm
(14.0
”
)
17.2 cm
(6.8
”
)
28.0 cm
(11.0
”
)
50.8 cm
(20.0
”
)
15.9 kg
(35 lb)