UPS WITH BYPASS ELECTRICAL INSTALLATION
EATON
Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide
S
164201393 Rev C
www.powerware.com
28
7.
Find the terminal strip inside the bypass switch cabinet. Using the
label on the back of the bypass switch access cover and the proper
installation wiring diagram, make the terminal strip connections and
tighten all connections as specified in Table 2 on page 22. Use
copper wire that is the appropriate size for the current draw.
Figure 17 shows a sample label.
Figure 17. Bypass Switch Wiring Label
8.
After installing bypass switch wiring, torque the screws holding all
input and output power conductors to the values specified in
Table 2 on page 22.