Chapter 9
Parallel Bypass
To switch the parallel UPS to maintenance bypass from Normal mode:
1.
From any UPS, set the system to internal Bypass mode:
S
Using the
button on the front panel display, scroll to the Control
menu option and press the
button.
S
Press the
button to select the Go to Bypass Mode option.
The
and
indicators illuminate, indicating the UPS system
is operating in Bypass mode.
2.
Switch the bypass breaker on the parallel tie cabinet to the ON
position.
3.
Switch the UPS breakers on the parallel tie cabinet to the OFF
position.