UPS INSTALLATION
Eaton 9355 UPS (10/15 kVA) User's Guide
S
164201594 Rev D
www.eaton.com/powerquality
22
Table 1. Terminal Block Wiring
10 kVA
Input Voltage
Wire
Function
Input Circuit
Breaker Size
L1, L2, L3, N
Wire Size
1
Ground
Wire Size
1
Tightening
Torque
Conduit Size
2, 3
(Number of Conduits)
208
Input
45A
6 AWG
10 AWG
120 lb in
(13.5 Nm)
1.00
”
conduit (1)
220
45A
8 AWG
10 AWG
480
(with transformer)
20A
12 AWG
12 AWG
600
(with transformer)
20A
12 AWG
14 AWG
208
Output
8 AWG
10 AWG
120 lb in
(13.5 Nm)
1.00
”
conduit (1)
220
8 AWG
10 AWG
480
(with transformer)
8 AWG
10 AWG
600
(with transformer)
8 AWG
10 AWG
15 kVA
Input Voltage
Wire
Function
Input Circuit
Breaker Size
L1, L2, L3, N
Wire Size
1
Ground
Wire Size
1
Tightening
Torque
Conduit Size
2, 3
(Number of Conduits)
208
Input
60A
4 AWG
10 AWG
120 lb in
(13.5 Nm)
1.25
”
conduit (1)
220
60A
4 AWG
10 AWG
1.25
”
conduit (1)
480
(with transformer)
30A
10 AWG
10 AWG
1.00
”
conduit (1)
600
(with transformer)
25A
10 AWG
10 AWG
1.00
”
conduit (1)
208
Output
6 AWG
10 AWG
120 lb in
(13.5 Nm)
1.00
”
conduit (1)
220
6 AWG
10 AWG
480
(with transformer)
6 AWG
10 AWG
600
(with transformer)
6 AWG
10 AWG
1
Use only 90
°
C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to National
Electrical Code
(NEC
)
Table 310‐16. Code may require a larger AWG size than shown in this table because of
temperature, number of conductors in the conduit, or long service runs. Follow local requirements.
2
Per NEC article 300‐20(a), all three-phase conductors must be run in the same conduit. Neutral and ground must be
run in the same conduit as the phase conductors.
3
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG
ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the
conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed.
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW‐2, TW, THW, THHW, THW‐2.