VERSION 2 WALL-MOUNTED BYPASS SWITCH
Eaton 9355 UPS (10/15 kVA) User's Guide
S
164201594 Rev D
www.eaton.com/powerquality
50
16.
Hardwire the load to the bypass cabinet (see Figure 35).
17.
Route the maintenance bypass wires through the conduit to the
UPS terminal block (see Figure 33 on page 48).
Connect the black and the red wires from the terminal block on the
Tie Cabinet to TB2 on the UPS.
NOTE
The maintenance bypass contacts are normally-open. To ensure proper bypass
operation, DO NOT use the blue wire (it is normally-closed).
18.
Replace the UPS wiring access cover and conduit landing plate.