Responding to System Events
12-2
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201554 Rev E
powerware.com
ALARMS
Message
Horn
Phone
Relay
Log* Indication
Battery Totally Discharged
1
No
1
HA
Shutdown Imminent
Battery Totally Discharged OK
Off
No
1
HA
Condition Cleared
Building Alarm 1
1
No
1
HA
User Action Required
Building Alarm 1 OK
Off
No
1
HA
Condition Cleared
Building Alarm 2
1
No
1
HA
User Action Required
Building Alarm 2 OK
Off
No
1
HA
Condition Cleared
Check Bypass
1
1
1
HA
Service Required
Check Bypass OK
Off
No
1
HA
Condition Cleared
Check Bypass Switchgear
1
No
1
HA
Service Required
Check Bypass Switchgear OK
Off
No
1
HA
Condition Cleared
Check Charger
1
1
1
HA
Service Required
Check Charger OK
Off
No
1
HA
Condition Cleared
Check Fan
1
No
1
HA
Service Required
Check Fan OK
Off
No
1
HA
Condition Cleared
Check Input Switchgear
1
1
1
HA
Service Required
Check Input Switchgear OK
Off
No
1
HA
Condition Cleared
Check Inv Temperature Sensor
1
No
1
HA
Service Required
Check Inv Temperature Sensor OK
Off
No
1
HA
Condition Cleared
Check Inverter
1
1
1
HA
Service Required
Check Logic Power Supply
1
No
1
HA
Service Required
Check Logic Power Supply OK
Off
No
1
HA
Condition Cleared
Check Output Switchgear
1
No
1
HA
Service Required
Check Output Switchgear OK
Off
No
1
HA
Condition Cleared
Check Power Supply
1
1
1
HA
Service Required
Check Power Supply OK
Off
No
1
HA
Condition Cleared
Check Precharge
1
No
1
HA
Service Required
Check Precharge OK
Off
No
1
HA
Condition Cleared
Check Rect Temperature Sensor
1
No
1
HA
Service Required
Check Rect Temperature Sensor OK
Off
No
1
HA
Condition Cleared
Check Rectifier
1
1
1
HA
Service Required
Check Static Switch
1
1
1
HA
Service Required
Check Static Switch OK
Off
No
1
HA
Condition Cleared
Close Battery Switchgear
1
1
1
HA
User Action Required
Close Battery Switchgear OK
Off
No
1
HA
Condition Cleared
*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and