Responding to System Events
12-4
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201554 Rev E
powerware.com
ALARMS
Indication
Log*
Relay
Phone
Horn
Message
L3 Overload (High Level)
1
No
1
HA
User Action Required
L3 Overload (High Level) OK
Off
No
1
HA
Condition Cleared
Low Battery Shutdown
1
No
1
HA
User Action Required
Low Battery Shutdown OK
Off
No
1
HA
Condition Cleared
Not Enough UPMs
1
No
1
HA
User Action Required
Not Enough UPMs OK
Off
No
1
HA
Condition Cleared
Output Overload
1
No
1
HA
User Action Required
Output Overload OK
Off
No
1
HA
Condition Cleared
Output Watts Overload
1
No
1
HA
User Action Required
Output Watts Overload OK
Off
No
1
HA
Condition Cleared
Parallel System Overload
1
No
1
HA
User Action Required
Parallel System Overload OK
Off
No
1
HA
Condition Cleared
Rect Overtemperature Trip
1
No
1
HA
Service Required
Rect Overtemperature Trip OK
Off
No
1
HA
Condition Cleared
Rectifier Overtemperature
1
No
1
HA
Service Required
Rectifier Overtemperature OK
Off
No
1
HA
Condition Cleared
Remote Emergency Power-off
1
No
1
HA
User Action Required
Remote Emergency Power-off OK
Off
No
1
HA
Condition Cleared
Selective Trip
1
1
1
HA
Service Required
Selective Trip OK
Off
No
1
HA
Condition Cleared
Shutdown Imminent
1
No
1
HA
User Action Required
Shutdown Imminent OK
Off
No
1
HA
Condition Cleared
Software Incompatibility
1
No
1
HA
Service Required
Software Incompatibility OK
Off
No
1
HA
Condition Cleared
Utility Out Of Limits
1
No
1
HA
User Action Required
Utility Out Of Limits OK
Off
No
1
HA
Condition Cleared
*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and
A = Active log only.
Summary of Contents for Powerware 9390-160/100
Page 1: ...Powerware 9390 UPS 100 160 kVA Installation and Operation Manual...
Page 225: ......
Page 226: ...164201554E 164201554 E...