POWER WIRING INSTALLATION NOTES
081505
C
164201554---5
NOTE:
Customer ground can be run in any conduit listed in Table J.
5 of 15
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-16
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201554 Rev E
powerware.com
Table I. UPS Cabinet Power Cable Terminations for the Powerware 9390---120/100,
9390---120/120, 9390---160/100, 9390---160/120 and 9390---160/160
(480V Input and 480V Output)
Terminal Function
Terminal Function Size of Pressure
Termination
Tightening
Torque
Nm (lb in)
Type
Screw
AC Input to UPS Rectifier
and Bypass
(Single Input)
E6
Phase A
2 --- #6---250
42.4 (375)
5/16 in. Hex
E7
Phase B
2 --- #6---250
42.4 (375)
5/16 in. Hex
E8
Phase C
2 --- #6---250
42.4 (375)
5/16 in. Hex
AC Input to UPS Rectifier
(Dual Input)
E1
Phase A
2 --- #6---250
42.4 (375)
5/16 in. Hex
E2
Phase B
2 --- #6---250
42.4 (375)
5/16 in. Hex
E3
Phase C
2 --- #6---250
42.4 (375)
5/16 in. Hex
AC Input To Bypass
(Dual Input)
E6
Phase A
2 --- #6---250
42.4 (375)
5/16 in. Hex
E7
Phase B
2 --- #6---250
42.4 (375)
5/16 in. Hex
E8
Phase C
2 --- #6---250
42.4 (375)
5/16 in. Hex
Single-Feed Jumper Bus
from Rectifier Input
Terminals to Bypass Input
Terminals
Rectifier
Phase A
N/A
12.5 (110)
M8 Hex Bolt
Bypass
Phase A
N/A
22.6 (200)
M10 Hex Bolt
Rectifier
Phase B
N/A
12.5 (110)
M8 Hex Bolt
Bypass
Phase B
N/A
22.6 (200)
M10 Hex Bolt
Rectifier
Phase C
N/A
12.5 (110)
M8 Hex Bolt
Bypass
Phase C
N/A
22.6 (200)
M10 Hex Bolt
AC Output to
Critical Load
E9
Phase A
2 --- #6---250
42.4 (375)
5/16 in. Hex
E10
Phase B
2 --- #6---250
42.4 (375)
5/16 in. Hex
E11
Phase C
2 --- #6---250
42.4 (375)
5/16 in. Hex
DC Input from
Battery to UPS
E4
Positive
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
E5
Negative
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
Input and Output Neutral
E12
Neutral
8 --- #6---250
42.4 (375)
5/16 in. Hex
Customer Ground
Ground
Ground
8 --- #14---1/0
5.6 (50)
Slotted