POWER WIRING INSTALLATION NOTES
081505
D
164201554---5
11 of 15
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-22
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201554 Rev E
powerware.com
28.
See Drawing 164201554---7 for UPM terminal locations and Table H or Table I for
termination requirements.
29.
Setup of the CAN Bridge card for parallel operation must be performed by an authorized
Eaton Customer Service Engineer
. Contact service to schedule a date.
30.
For parallel system circuit breaker ratings, see appropriate information in Table N.
31.
For parallel system ratings, see the appropriate information in Table O through Table Q.
Table N. Recommended UPM Output (MOB), Main Output (MIS), and Bypass (MBP)
Circuit Breaker Ratings
UPM Model
Configuration
Output Voltage
208V/220V
480V
MOB
MIS
MBP
MOB
MIS
MBP
9390---120/100
9390---160/100
1+1
500
500
500
200
200
200
2+0 and 2+1
500
1000
1000
200
400
400
3+0 and 3+1
500
1600
1600
200
600
600
4+0
500
2000
2000
200
800
800
9390---120/120
9390---160/120
1+1
500
500
500
200
200
200
2+0 and 2+1
500
1000
1000
200
400
400
3+0 and 3+1
500
1600
1600
200
600
600
4+0
500
2000
2000
200
800
800
9390---160/160
1+1
600
600
600
250
250
250
2+0 and 2+1
600
1200
1200
250
500
500
3+0 and 3+1
600
2000
2000
250
800
800
4+0
600
2400
2400
250
1000
1000
Summary of Contents for Powerware 9390-160/100
Page 1: ...Powerware 9390 UPS 100 160 kVA Installation and Operation Manual...
Page 225: ......