Installing the UPS System
3-7
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201554 Rev E
powerware.com
C A U T I O N
DELTA SOURCES (TN-S) - The 9390 UPS system can be operated only from a delta supply
source that is fully floating and if the neutral-forming transformer kit (PN 103005400) is
installed in the UPS. The UPS cannot be operated from a mid-point or end-point grounded
delta supply source. With this type of supply source, there is no capability to provide an output
neutral.
In no circumstances shall a neutral to ground bonding jumper be installed in the
UPS.
3.2.6.1 208V/220V Input External Wiring Installation
To install wiring to connections:
1.
Slide the air filters up and remove them from the cabinet.
2.
Remove the screws securing the control panel door and swing the door open.
3.
Remove the screws securing the bottom internal safety shield panel and remove
the panel to gain access to the input, output, and battery terminals. Retain the
hardware for later use.
4.
If installing power wiring from the top of the cabinet, proceed to Step 5;
otherwise, proceed to Step 6.
5. FOR TOP ACCESS WIRING
- Remove the screws securing the top internal safety
shield panel and remove the panel to gain access to the top wiring entry. Retain
the hardware for later use. Remove the top conduit plate from its storage location
on the top of the UPS. Identify all conduit requirements and mark their location.
Drill and punch all conduit holes in top conduit plate prior to mounting on UPS.
Install conduit plate and install all conduit runs into plate. Pull wiring through
conduit into UPS wiring area.
6. FOR BOTTOM ACCESS WIRING
- Remove the bottom conduit plate from its
location on the bottom of the UPS. Identify all conduit requirements and mark
their location. Drill and punch all conduit holes in bottom conduit plate prior to
mounting on UPS. Install conduit plate and install all conduit runs into plate. Pull
wiring through conduit into UPS wiring area.
7.
Route the input and output cables to the UPS terminal blocks. See Drawing
164201554-7 starting on page A-29 for wiring access information and terminal
locations.
8.
If wiring a single-feed system, proceed to Step 9; if wiring a dual-feed system,
proceed to Step 11.
9.
Connect phase A, B, C, and Neutral (if required) input power wiring from the
utility source to the rectifier input terminals and neutral terminals in the UPS
cabinet. See Appendix A for wiring and termination requirements and wiring
access information. Note wiring connections for single-feed systems.
10.
Proceed to Step 14.