013106
B
164201590---6
IAC POWER TERMINAL LOCATIONS
GROUND TERMINALS
MAINTENANCE
BYPASS SWITCH (MBP)
(SEE SHEET 15 of 22
FOR DETAILS)
MAINTENANCE
ISOLATION SWITCH (MIS)
(SEE SHEET 15 of 22 FOR DETAILS)
AC OUTPUT TO CRITICAL LOAD
(A, B, C)
AC INPUT TO BYPASS
FROM UTILITY (A, B, C)
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
GROUND TERMINALS
NEUTRAL TERMINALS
1+1 PARALLEL REDUNDANT CONFIGURATION
WITH MAINTENANCE BYPASS
MODULE OUTPUT
BREAKER 2 (MOB 2)
MODULE OUTPUT
BREAKER 1 (MOB 1)
(SEE SHEET 14 of 22
FOR DETAILS)
AC INPUT FROM UPM 2
(A, B, C)
(SEE SHEET 14 of 22 FOR DETAILS)
AC INPUT FROM UPM 1
(A, B, C)
NOTE:
1. Metal shields covering wiring
terminals must be removed to gain
access to terminals.
2. 100 kVA model must be wired for
120 kVA.
160/100, 160/120, AND 160/160 kVA 208V/208V
120/100 AND 120/120 kVA 208V/208V
4 of 22
Installation Information
A-37
EATON
Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual
S
164201590 Rev C