Chapter 6
Maintaining the IAC
The components inside the Integrated Accessory Cabinet (IAC) are secured to a sturdy
metal frame. All repairable parts and assemblies are located for easy removal with very
little disassembly. This design allows authorized service personnel to perform routine
maintenance and servicing quickly.
6.1 Important Safety Instructions
Remember that the UPS system is designed to supply power
EVEN WHEN
DISCONNECTED FROM THE UTILITY POWER
. The IAC interior is unsafe until the UPS is
shut down (inverter output and bypass) and bypass utility power to the IAC is
disconnected.
W A R N I N G
쑺
Servicing and maintenance should be performed by qualified service personnel only.
쑺
LETHAL VOLTAGE PRESENT. This unit should not be operated with the cabinet doors open
or protective panels removed. Do not make any assumptions about the electrical state of
any cabinet in the UPS system.
6.2 Performing Preventive Maintenance
The IAC requires very little preventive maintenance. However, the system should be
inspected periodically to verify that the unit is operating normally.
6.2.1 DAILY Maintenance
Perform the following steps daily:
1.
Check the area surrounding the IAC. Verify the area is not cluttered, allowing free
access to the unit.
2.
Verify the air intakes (vents on the front of the cabinet) and exhaust opening (on
top of the IAC) are not blocked.
3.
Verify the operating environment is within the parameters specified in Chapter 7,
“Product Specifications”, and Drawing 164201590-2 on page A-6.
4.
Record the check results and any corrective actions in a suitable log.