POWER WIRING INSTALLATION NOTES
013106
B
164201590---4
3 of 13
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-21
EATON
Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual
S
164201590 Rev C
powerware.com
Table G
.
INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9390 IAC 40–80 kVA 480V
(1+1 Parallel Redundant Configuration with Maintenance Bypass)
Units
Rating 50/60 Hz
Basic Unit Rating
KVA
40
50
60
80
Input and Bypass Input
Output
VOLTS
VOLTS
480
480
480
480
480
480
480
480
AC Input from UPM
(Standalone Installation)
Full Load Current for each Module
(3) Phases, (1) Ground
D
AMPS
48
60
72
96
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
For contractor-supplied wiring, refer to the applicable
Powerware 9390 UPS Installation and Operation manual,
listed in paragraph 1.5. Wiring for line-up-and-match
installation is factory-supplied.
Neutral (if required)
Minimum Conductor Size
Number
AWG or kcmil
(each)
2
(1)
2
(1)
1
(1)
1/0
(1)
AC Input to Maintenance Bypass
(Line-up-and-Match or Standalone Installation)
(3) Phases, (1) Ground
E
AMPS
48
60
72
96
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
4
(1)
2
(1)
1
(1)
1/0
(1)
Neutral (if required)
Minimum Conductor Size
Number
AWG or kcmil
(each)
2
(1)
2
(1)
1
(1)
1/0
(1)
AC Output to Critical Load
(Line-up-and-Match or Standalone Installation)
Full Load Current
(3) Phases, (1) Ground
F
AMPS
48
60
72
96
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
4
(1)
2
(1)
1
(1)
1/0
(1)
Neutral (if required)
Minimum Conductor Size
Number
AWG or kcmil
(each)
2
(1)
2
(1)
1
(1)
1/0
(1)
NOTE:
Callout letters
D, E,
and
F
map to drawing 164201590---3, sheet 11 of 11.
Summary of Contents for Powerware 9390 IAC-B
Page 145: ......
Page 146: ...164201590C 164201590 C...