INSTALLATION
Eaton 9390 UPS, 9395 UPS, and 9395 SSBM Sync Control Installation and Operation Manual
S
P-164000052 Rev 2
3-15
Cable Exit Opening for
1/2” Conduit
Plug-in Terminal Block J2 from
Relay Contacts to Customer's
Monitoring Equipment
Figure 3‐13. Industrial Relay Card
Table 3‐3. IRC Wire Terminations
IRC Terminal
Function
Remarks
J2-1
NC
Normal Mode
J2-2
COM
J2-3
NO
J2-4
NC
Bypass Mode
J2-5
COM
J2-6
NO
J2-7
NC
Battery Mode
J2-8
COM
J2-9
NO
J2-10
NC
Alarm Mode
J2-11
COM
J2-12
NO
NOTE
Maximum contact rating: 250 Vac, 30 Vdc @ 5A Wire Range: 16–24 AWG