UPS OPERATING INSTRUCTIONS
Eaton 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual
S
164201716 Rev 2
www.eaton.com/powerquality
7-43
3.
On the System Status screen, select the
UPM
Command. The UPS Control
Command screen is displayed.
4.
On the UPS Control Command screen, select the UPM to shut down.
5.
Press the
CONTROLS
pushbutton on the UPS Control Command menu bar. The
UPM Control Command screen is displayed.
6.
Proceed to Step 9.
7.
On the System Status screen, select the
UPM
command.
8.
Press the
CONTROLS
pushbutton on the System Status Command menu bar. The
UPM Control Command screen is displayed.
9.
On the UPM Control Command screen, select
UPM OFF
.
10.
Press the
SELECT
pushbutton on the UPM Command menu bar.
The UPM status indicates
READY
.
The input, output, and battery contactors
open, and the power module remains on. The remaining UPMs supply the
critical load.
11.
To turn off the power module, press the
CONTROLS
pushbutton on the UPS
Control Command menu bar. The UPM Control Command screen is displayed.
12.
On the UPM Control Command screen, select
UPM OFF
.
13.
Press the
SELECT
pushbutton on the UPM Command menu bar.
The UPM status indicates
SHUTDOWN
.
The power module is turned off. The
remaining UPMs continue to supply the critical load.
Logic power remains on.
7.4.21
Single UPM Restart
To restart a single UPM from a shutdown state:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status
screen is displayed.
2.
If UPM 4 (FI-UPM) is installed, proceed to Step 3; otherwise, proceed to Step 7.
3.
On the System Status screen, select the
UPM
command. The UPS Control
Command screen screen is displayed.
4.
On the UPS Control Command screen, select the UPM to restart.
5.
Press the
CONTROLS
pushbutton on the UPS Control Command menu bar. The
UPM Control Command screen is displayed.
6.
Proceed to Step 9.
7.
On the System Status screen, select the
UPM
command.
8.
Press the
CONTROLS
pushbutton on the System Status Command menu bar. The
UPM Control Command screen is displayed.
9.
On the UPM Control Command screen, select
UPM ON
.
10.
Press the
SELECT
pushbutton on the UPM Command menu bar.