UPS OPERATING INSTRUCTIONS
Eaton 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual
S
164201716 Rev 2
www.eaton.com/powerquality
7-49
W
A
R
N
I
N
G
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
To use the
LOAD OFF
command:
1.
Press the
CONTROLS
pushbutton on the main menu bar of the UPS to be shut
down. The System Status screen is displayed.
2.
On the System Status screen, select either the
UPS
or the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS or
Bypass Control Command screen is displayed.
4.
On the Control Command screen, select
LOAD OFF
.
5.
Press the
SELECT
pushbutton on the Command menu bar.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
C
A
U
T
I
O
N
All power to the critical load is lost when LOAD OFF is selected in the following step. You should use this
feature only when you want to de‐energize the critical load.
6.
To shut down the UPS, press
LOAD OFF
from the Load Off menu bar, and hold for
three seconds. To abort the shutdown, press
CANCEL
.
When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off on the UPS.
7.
If another UPS is to be shut down, proceed to that UPS and repeat
Steps 1 through 6.
C
A
U
T
I
O
N
Do not attempt to restart the system after the Load Off until the cause of the shutdown has been identified
and cleared.
8.
Restart the UPS after pressing the
LOAD OFF
pushbutton by following the
procedure in paragraph 7.4.1 on page 7-30 or 7.4.8 on page 7-34.
W
A
R
N
I
N
G
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.