Eaton 9395/9395P UPS (1000–1200 kVA) Single Feed Kit Installation Instructions  

S

  P-1640000610 Rev 1

  www.eaton.com/powerquality

1

Eaton 9395/9395P UPS (1000–1200 kVA) Single-Feed Kit Installation

NOTE  

Refer to the applicable installation and operation manual supplied with the UPS during  installation.

W

 

A

 

R

 

N

 

I

 

N

 

G

Installation should be performed only by qualified personnel.

To install the single-feed kit:

1.

If not already accomplished, remove one top screw and two bottom screws
securing each ISBM section left and right front panel (refer to the applicable
Eaton 9395/9395P UPS manual for panel location). Lift the panels straight up to
remove them from the panel hanger brackets at the top of the cabinet.

2.

If not already accomplished,remove the screws securing the top and bottom
internal safety shield panels and remove the panels to gain access to the rectifier
and bypass input terminals. Retain the hardware for later use.

3.

Using M12 hardware from the UPS external wiring terminal hardware kit, install
the single-feed bus bar extensions (see Table 1) onto the back side of the
rectifier input bus bars (see Figure 1). Mount the extension bar using the two
rear holes on the bus bar. Tighten the bolts to the torque values in Table 2.

4.

Using M12 hardware from the UPS external wiring terminal hardware kit, install
the single-feed jumper cables from the kit (see Table 1) between the rectifier
input bus bar extension and the bypass input terminal (see Figure 1). Verify each
rectifier phase terminal is jumpered to the same phase on the bypass terminal.
Use the two bottom rear holes on the bus bar extensions and bypass input bus
bars. Tighten the bolts to the torque values listed in Table 2.

Table 1. Supplied Terminal Hardware

Part

Size

Quantity

Terminals Used On

Eaton Part Number

Jumper Cable

N/A

12 (4 per phase)

Rectifier and Bypass Input

152602719 (wire kit with 12 cables)

Bus Bar Extension

N/A

3

Rectifier Input

119201546

Bolt, Grade 5

M12

 

60 mm

18

Rectifier and Bypass Input

180190078-117

Tie Wrap

0.30

  W

 

14.5

 L

9

Jumper Cables

152201082

Table 2. Single-Feed Power Cable Terminations

Terminal Function

Terminal

Function

Bus Landing

Tightening Torque Nm (lb ft)

Bolt Size

Bus Bar Extension
(Not required on 600V)

E1

Phase A

2 – 1 bolt mounting

76 (56)

M12

E2

Phase B

2 – 1 bolt mounting

76 (56)

M12

E3

Phase C

2 – 1 bolt mounting

76 (56)

M12

Rectifier Input

E1

Phase A

2 – 1 bolt mounting

76 (56)

M12

E2

Phase B

2 – 1 bolt mounting

76 (56)

M12

E3

Phase C

2 – 1 bolt mounting

76 (56)

M12

Bypass Input

E6

Phase A

2 – 1 bolt mounting

76 (56)

M12

E7

Phase B

2 – 1 bolt mounting

76 (56)

M12

E8

Phase C

2 – 1 bolt mounting

76 (56)

M12