EATON 9395/9395P UPS (1000–1200 KVA) SINGLE-FEED KIT INSTALLATION
Eaton 9395/9395P UPS (1000–1200 kVA) Single Feed Kit Installation Instructions
S
P-1640000610 Rev 1
www.eaton.com/powerquality
2
5.
Using tie wraps from the single-feed kit (see Table 1), secure cables to the
internal cabinet divider (see Figure 1).
6.
Return to the applicable Eaton 9395/9395P UPS manual to complete the wiring.
Use M12
60mm bolts from the single-feed kit (see Table 1) to install rectifier
input lugs.
Rectifier Input Terminal (Phase C; Phase A on 600V)
Bypass Input Terminal (Phase C)
1 M12
50mm Bolt, 2 Flat
Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)
1 M12
60mm Bolt from
Single-Feed Hardware Kit
(18 places)
2 Flat Washers, 1 Conical
Washer, and 1 Nut from
UPS Hardware Kit (18 places)
1 M12
50mm Bolt, 2 Flat
Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)
1 M12
50mm Bolt, 2 Flat
Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)
NOTE
Install bus bar extensions to back side of rectifier input bus bars to provide clearance for bolts and wires.
NOTE
Verify each rectifier phase terminal is jumpered to the same phase on the bypass terminal.
NOTE
Install rectifier input lugs using M12
60mm bolts from the single-feed kit.
Tie Wraps (6 places)
Front
Bus Bar Extension
Rectifier Input Terminal (Phase B)
Bus Bar Extension (Not required on 600V)
Single Feed Jumpers from Kit (4 per phase)
Rectifier Input Terminal (Phase A; Phase C on 600V)
Bus Bar Extension
Single Feed Jumpers from Kit (4 per phase)
Single Feed Jumpers from Kit (4 per phase)
Bypass Input Terminal (Phase A)
Bypass Input Terminal (Phase B)
Figure 1. 9395/9395P 1000–1200 kVA UPS Single-Feed Kit