EATON 9395/9395P UPS (1000–1200 KVA) SINGLE-FEED KIT INSTALLATION

Eaton 9395/9395P UPS (1000–1200 kVA) Single Feed Kit Installation Instructions  

S

  P-1640000610 Rev 1

  www.eaton.com/powerquality

2

5.

Using tie wraps from the single-feed kit (see Table 1), secure cables to the
internal cabinet divider (see Figure 1).

6.

Return to the applicable Eaton 9395/9395P UPS manual to complete the wiring.
Use M12

 

60mm bolts from the single-feed kit (see Table 1) to install rectifier

input lugs.

Rectifier Input Terminal (Phase C; Phase A on 600V)

Bypass Input Terminal (Phase C)

1 M12

 

50mm Bolt, 2 Flat

Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)

1 M12

 

60mm Bolt from

Single-Feed Hardware Kit
(18 places)
2 Flat Washers, 1 Conical
Washer, and 1 Nut from
UPS Hardware Kit (18 places)

1 M12

 

50mm Bolt, 2 Flat

Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)

1 M12

 

50mm Bolt, 2 Flat

Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)

NOTE  

Install bus bar extensions to back side of rectifier input bus bars to provide clearance for bolts and wires.

NOTE  

Verify each rectifier phase terminal is jumpered to the same phase on the bypass terminal.

NOTE  

Install rectifier input lugs using M12

 

60mm bolts from the single-feed kit.

Tie Wraps (6 places)

Front

Bus Bar Extension

Rectifier Input Terminal (Phase B)

Bus Bar Extension (Not required on 600V)

Single Feed Jumpers from Kit (4 per phase)

Rectifier Input Terminal (Phase A; Phase C on 600V)

Bus Bar Extension

Single Feed Jumpers from Kit (4 per phase)

Single Feed Jumpers from Kit (4 per phase)

Bypass Input Terminal (Phase A)

Bypass Input Terminal (Phase B)

Figure 1. 9395/9395P 1000–1200 kVA UPS Single-Feed Kit