Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications
26
Powerware 9910-E64
4200 Watt/6000 VA, 208-240 Vac UPS
Features and Benefits
•
Isolates connected equipment from all incoming power problems to
provide the highest degree of protection with rugged, online design
•
Conservers valuable space with compact design
•
Significantly increases battery service life and gives you advanced warning of the end of useful
battery life with ABM technology
•
Prolongs backup time with 3U Extended Battery Modules
•
Tested and approved by IBM to assure out-of-box usability
•
Includes premium IBM warranty
E64 Model Guide
Model
Number
IBM
Number
Power Out
(Watts/VA)
Input
Connection
2
Output
Connection
Dimensions
(HxWxD, in/mm)
Unit
Weight
(lb/kg)
3
208-240 Vac; 50/60 Hz auto-sensing
9910-E64
1
42R8073
4200/6000
L6-30AR
(1) L6-30R
8.75 (5U) x 17 x 24.9/
219 x 432 x 633
206/93.6
Extended Battery Module (EBM)
9910-6645 42R8076 —
—
—
5.25 (2U) x 17 x 24.75/
133 x 432 x 628
169/76.8
1. Base configuration of the E64 consists of E64 Accessory Kit (IBM p/n 42R8074) and two UPS internal battery trays
(IBM p/n 42R4316). 2. Input power cord is 1.5 ft/0.5m. Requires input power cord supplied by IBM. Types vary. See
Line Cord Options table. 3. Weight includes batteries.
E64 Battery Runtimes Chart (in Minutes)
Load in Watts
UPS Internal Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
1400 38
108
186 271 362
2100 34
70 122
178 237
2800
19
49 86
125 168
3500
13
37 65
96 128
4200
10
30 52
76 102
Note: This guide provides typical application information. Battery times are approximate and may vary with equipment,
configuration, disk access, battery age, temperature, etc.
E64 UPS Rear Panel