P14 Technical Specifications*
Electrical Input
Nominal Voltage
230 Vac (user selectable to 220 Vac)
Online Voltage Range
±20% for nominal voltage at full load
Nominal Input Frequency
45–65 Hz, 50/60 Hz; auto-sensing
Input Protection
Reset-able circuit breaker
Connection IEC-320-C14
Electrical Output
Power Levels
950W/1400 VA
Online Regulation
-10%, +6% of nominal voltage
On Battery Voltage Regulation
±5% of nominal voltage; -10% after low battery warning
On Battery Frequency Regulation
±0.1 Hz of nominal frequency
Voltage Wave Shape
Sine wave (during normal and battery operation)
Connections (6)
IEC-320-C13
Indicators and Controls
Front Panel LEDs
Power on, on battery, overload, and battery fault
Front Panel Buttons
On/off and alarm silence/self-test
Communication Port
DB-9 female (UPS ships with communication cable); USB Interface Adapter is
optional
Battery
Battery Type
Sealed, maintenance-free lead-acid; starved electrolyte
Battery Description
(3) 12V, 9 Ah
Battery Recharge
<3 hours to 90% capacity
Battery Runtime
See Battery Runtimes table
Start-On-Battery
Startup with UPS batteries in absence of utility power
General
Topology Line-interactive
Diagnostics 0.68
Dimensions and Weight
See Model Guide
Network Transient Protector
In and out RJ-11 jack for telephone/modem protection or RJ-45 for 10BaseT network
cable; UL497A tested
Environmental and Safety
Operating Temperature
0°C to 40°C (32°F to 104°F) UL tested at 25°C (77°F)
Transit/Storage Temp.
-15°C to 55°C (5°F to 131°F)
Heat Dissipation
189 BTU/hr, maximum
Audible Noise
<45 dBA typical
Relative Humidity
5% to 95% noncondensing
Safety Markings
UL, cUL, and CSA
Safety Conformance
UL 1778, CAN/CSA C22.2, No. 107.1
EMC Markings
FCC Class B; 230V models also CE (EN50091-2) and C-Tick
Surge Suppression
ANSI C62.41 Category A (formerly IEEE 587)
Immunity
IEC 801-2, -3, -4
* Due to continuing product improvement programs, specifications subject to change without notice.