Eaton 9910 UPS and EBM Installation Guide (6000 VA Models)
S
P-164000007 Rev 1
17
Chapter 3
Installation
The 9910 UPS and Extended Battery Module (EBM) can be purchased
separately or factory-installed in an IBM rack.
NOTE
Review “Preparation” on page 1 and the following “Installation Precautions,” and
then follow the procedures in this chapter that apply to your installation.
Installation Precautions
Before you install or connect the UPS or EBM in a rack cabinet, observe
the following precautions:
S
Read and understand all warnings and cautions listed in “Safety
Warnings” on page 5.
S
Review the documentation that comes with your rack cabinet for
safety and cabling information.
NOTE
Removing the rack doors and side panels might make installation easier. See the
rack cabinet documentation for more information.
S
Verify that the room air temperature is below 35
°
C (95
°
F).
S
Do not block any air vents. Usually 15 cm (6 in.) of air space provides
proper airflow.
S
Take all necessary precautions to handle the weight of the devices.
C
A
U
T
I
O
N
The UPS and
EBM
are heavy (see Table 10). Use at least the minimum number of people
required to lift the cabinets into the rack.
Table 10. Weights
UPS
EBM
Weights
72 kg (159 lb) total weight
24 kg (53 lb) internal battery each of two
24 kg (53 lb) cabinet only
59 kg (130 lb)
Handling Requirement
Cabinet only: Two persons
Single battery only: Two persons
Specially trained persons, a lifting device,
or both