Racks and Power Distribution
Racks and Power Distribution
Racks and Power Distribution
Eaton, Powerware, and BladeUPS are trade names, trademarks, and/or
service marks of Eaton Corporation and its subsidiaries or affiliates.
© 2008 Eaton Corporation, All Rights Reserved.
1018037 Rev C
UPS ProdUctS and acceSSorieS
Power
Rack Space
Configuration
Parts
Qty
Description
Required
36kW N+1 ZC122P060100000 4 Powerware BladeUPS
24U
12 kW 400V w/parallel cord,
7.7 min battery @ 36 kW
103005913
1 Powerware 42U enclosure
6U
with BladeBar and
Bottom WW
116750221-001
1 ConnectUPS-X WEB/SNMP
-
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1
12U
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591
4 Battery increase to 18 minutes 12U
battery runtime*
8 Battery increase to 28 minutes 24U
12 Battery increase to 37 minutes 36U
16 Battery increase to 47 minutes 48U
* Each UPS requires same number of external batteries
Six (6) rackS @ 6 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000 1
Powerware Rack Power Module
3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 2
Powerware Rack Power Module
0U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08
6
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052736
6
42U Enclosure (Rack) Split Rear &
-
Casters no Sides
1052754
5
Powerware Baying Kit,
-
to attach two racks together
Total U space remaining for IT equipment
243U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
three (3) rackS @ 12 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000 2
Powerware Rack Power Module
6U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032420CD100000 1
Powerware Rack Power Module (RPM), 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 15 ft
PW107BA0UC08
6
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052736
3
42U Enclosure (Rack) Split Rear &
-
Casters no Sides
1052754
2
Powerware Baying Kit,
-
to attach two racks together
Total U space remaining for IT equipment
117U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
UPS ProdUctS and acceSSorieS
Power
Rack Space
Configuration
Parts
Qty
Description
Required
48kW N+1 ZC122P060100000 5 Powerware BladeUPS
30U
12 kW 400V w/parallel cord,
6.9 min battery @ 48 kW
103005913
1 Powerware 42U enclosure
6U
with BladeBar and
Bottom WW
116750221-001
1 ConnectUPS-X WEB/SNMP
-
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1
6U
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591
5 Battery increase to 17 minutes 15U
battery runtime*
10 Battery increase to 26 minutes 30U
15 Battery increase to 34 minutes 45U
20 Battery increase to 44 minutes 60U
* Each UPS requires same number of external batteries
UPS ProdUctS and acceSSorieS
Power
Rack Space
Configuration
Parts
Qty
Description
Required
60kW N+1 ZC122P060100000 6 Powerware BladeUPS
36U
12 kW 400V w/parallel cord,
6.9 min battery @ 48 kW
103005913
1 Powerware 42U enclosure
6U
with BladeBar and
Bottom WW
116750221-001
1 ConnectUPS-X WEB/SNMP
-
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1
0U
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591
6 Battery increase to 15 minutes 18U
battery runtime*
12 Battery increase to 22 minutes 36U
18 Battery increase to 29 minutes 54U
24 Battery increase to 37 minutes 72U
* Each UPS requires same number of external batteries
eiGht (8) rackS @ 6 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000 1
Powerware Rack Power Module
3U
12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 3
Powerware Rack Power Module (RPM), 9U
12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08
8
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052736
8
42U Enclosure (Rack) Split Rear &
-
Casters no Sides
1052754
7
Powerware Baying Kit,
-
to attach two racks together
Total U space remaining for IT equipment
324U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
FoUr (4) rackS @ 12 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000 1
Powerware Rack Power Module
3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out BladeUPS Plug, 10 ft
Y032440CD100000 3
Powerware Rack Power Module
9U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08
8
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052736
4
42U Enclosure (Rack) Split Rear &
-
Casters no Sides
1052754
3
Powerware Baying Kit,
-
to attach two racks together
Total U space remaining for IT equipment
156U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
Five (5) rackS @ 12 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000 2
Powerware Rack Power Module
6U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 3
Powerware Rack Power Module (RPM), 9U
12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08
10
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052736
5
42U Enclosure (Rack) Split Rear &
-
Casters no Sides
1052754
4
Powerware Baying Kit,
-
to attach two racks together
Total U space remaining for IT equipment
195U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
**ten (10) rackS @ 6 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000 1
Powerware Rack Power Module
3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 4
Powerware Rack Power Module
12U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08
10
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
-
1052736
10
42U Enclosure (Rack) Split Rear &
Casters no Sides
1052754
9
Powerware Baying Kit,
-
to attach two racks together
Total U space remaining for IT equipment
405U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
** When supporting more than eight racks it is recommended to place UPS in center of configuration
to make power distribution wiring easier.
BELGIUM
Tel: +32 (0) 2 348 4410
CZECH
Tel: +420 272 760 365
UPSInfoCzech@eaton.com
DENMARK
Tel: +45 3686 7910
UPSSalesDenmark@eaton.com
FINLAND
Tel: +358 9 452 661
PowerwareMyynti@eaton.com
FRANCE
Tel: +33 1 60 12 74 00
powerware.france@eaton.com
GERMANY
Tel: +49 7841 6040
infogermany@eaton.com
ITALY
Tel: +39 02 95542 309
info@powerware.it
NORWAY
Tel: +47 23 03 65 50
SalesNorway@eaton.com
POLAND
Tel: +48 22 331 85 24
upssalespoland@eaton.com
RUSSIA
Tel: +7 495 981 37 70
UPSRussia@eaton.com
SLOVAKIA
Tel: +421 2 4463 7046
InfoSk@Eaton.com
SPAIN
Tel: +34 475 32 03
infoespana@eaton.com
SWEDEN
Tel: +46 8 598 940 00
infosweden@eaton.com
THE NETHERLANDS
Tel: 0800–8774636
UAE
Tel: +971 4 881 19 33
Fax: +971 4 881 1939
UNITED KINGDOM
Tel: +44 1753-608 700
acukpowerware@eaton.
com