SPECIFICATIONS
EATON
Powerware
®
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 3
www.powerware.com
116
Table 13. Electrical Output
BladeUPS 12
BladeUPS 12i
Nominal Output Voltage
120/208 Vac three-phase
230/400 Vac three-phase
Output Voltage Variation
(Standard)
104–132 Vac phase to neutral,
180–229 Vac phase to phase
207–253 Vac phase to neutral,
358–438 Vac phase to phase
Output Voltage Variation
(Reduced)
108–132 Vac phase to neutral,
187–229 Vac phase to phase
Not applicable
Output Receptacles
Anderson connector
Anderson connector
Short Circuit Capability
(Battery Mode)
84A, <300 ms
44A, <300 ms
Short Circuit Capability
(Normal Mode)
Limited by 50A input breaker
Limited by 30A input breaker
Nominal Output Frequency
50–60 Hz auto-detection (Normal mode)
50 or 60 Hz (Battery mode)
Output Frequency Variation
Synchronized (Normal mode)
±0.1 when not synchronized with source (Battery mode)
Output Overload
100–110%: load transfers to Bypass mode after 10 minutes
110–125%: load transfers to Bypass mode after 1 minute
125–150%: load transfers to Bypass mode after 5 seconds
>150%: load transfers to Bypass mode after 300 ms
Voltage Waveform
Normal mode and Battery mode: Sine wave; <2% THD with linear load;
<5% with nonlinear load
Full Output
Three-phase