INSTALLATION
EATON
Powerware
®
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 3
www.powerware.com
69
9.
Verify that the “Batteries Disconnected” alarm on each UPS has
cleared. Verify that no other alarms appear on any UPS front panel
display.
If an
indicator is flashing on any UPS, do not proceed until all
alarms are clear. Check the UPS status from the front panel to view
the active alarms. Correct the alarms and restart if necessary.
10.
On any UPS, press any button on the front panel display to activate
the menu options, and then press the button until the TURN UPS
ON/OFF menu displays.
11.
Press the
button to display the TURN SYSTEM ON option; press
the
button.
12.
Confirm the selection. Press and hold the
button for three
seconds, until the UPS stops beeping.
Verify that the
indicator illuminates solid on each UPS,
indicating that the UPS is operating normally and any loads not
connected through the load connector are now energized.
If the
indicator on any UPS is flashing, do not proceed until all
alarms are clear. Check the UPS status from the front panel to view
the active alarms. Correct the alarms and restart if necessary.
Each UPS should be in Normal mode. By default, Normal mode
operates on the High Efficiency setting (see “Normal Mode” on
page 76).
13.
To energize loads connected through the load connectors, switch all
load connector circuit breakers to the ON (
|
) position.
14.
On any UPS, press the
ESC
button until the Eaton Powerware logo
appears.
15.
If optional EBMs are installed, see “Configuring the UPS for EBMs”
on page 87 to set the number of installed EBMs for each UPS.