OPERATION
EATON
Powerware
®
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 3
www.powerware.com
86
Transferring the UPS Between Modes
From Normal to Bypass Mode
. Press any button to activate the menu
options, then select CONTROL and GO TO BYPASS MODE.
From Bypass to Normal Mode
. Press any button to activate the menu
options, then select CONTROL and GO TO NORMAL MODE.
Alternatively (standalone UPS only): Press any button to activate the
menu options, then select TURN UPS ON/OFF, TURN UPS ON, and OK
to confirm.
Setting Power Strategy
To set the power strategy:
1.
Press any button to activate the menu options, then select
SETTINGS, USER SETTINGS, and POWER STRATEGY.
2.
Select HIGH EFFICIENCY or STANDARD, and OK to confirm.
NOTE
Time in the Standard power strategy is limited to 60 minutes when commanded
through the front panel. The setting then automatically returns to High Efficiency.