Configuring Battery Settings
Set the UPS for the number of EBMs installed, whether to run automatic
battery tests, and the level for the Battery Low alarm.
Configuring the UPS for EBMs
To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:
1.
Press any button on the front panel display to activate the menu
options, then select SETTINGS, USER SETTINGS, BATTERY
SETUP, and NUMBER OF ERMS.
2.
Use the or buttons to select the number of EBMs according to
your UPS configuration:
All UPS and EBM Cabinets
Number of EBMs
UPS only
0 (default)
UPS + 1 EBM
1
UPS + 2 EBMs
2
UPS + 3 EBMs
3
UPS + 4 EBMs
4
3.
Press the
button to save the setting.
4.
Press the
ESC
button until the Eaton Powerware logo appears.
Running Automatic Battery Tests
Battery tests rely on backfeeding the utility, using the utility as a load.
Some sites may choose to disable battery testing if their source is not
capable of being backfed. Examples of such sources include generators,
other UPSs, and other stiff or soft sources.
If a test is run on a source not capable of being backfed, the BladeUPS
will abort the test (due to utility failure) and will maintain the load and log
the event. Further consequences depend on the source (for example,
another UPS feeding the BladeUPS may trip off).