CONFIGURATION
EATON
Powerware
®
Environmental Rack Monitor (ERM) User’s Guide
S
164201673 Rev 1
9
4.
Set the serial line to 9600 baud, 8 data bits, No parity, 1 stop bit,
and no flow control (see Figure 7).
Figure 7. COM1 Properties Screen
5.
After a few seconds, the Password prompt appears (see Figure 8).
If the Password prompt does not appear, check the following
conditions:
S
Verify that the serial cable is connected to the RJ-45 connector
labeled “TH-Module-2“ on the ERM.
S
Verify the serial line is set to 9600 baud, No parity, 8 data bits,
1 stop bit, and no flow control.
S
If the serial line settings are correct, check the cabling to verify
all connections are secure.
S
Verify that your terminal program is on the correct
communication port for the serial connection.
S
Verify that the ERM has power (one or more LEDs on the ERM
are illuminated). The ERM should be turned on.