background image

Figure 5. 

Install Configuration Cable

Figure 6. 

Select Connection

Figure 7. 

Configure Port Settings

Figure 8. 

Enter Configuration Password

Eaton

®

 ConnectUPS

t

 Web/SNMP Card (X and BD Models) Quick Start Instructions 164950185Rev B

www.eaton.com/powerquality

6

Section 2

Connect the Card

To connect the card to the computer and start the configuration:

1.

Plug the RJ-45 end of the supplied configuration cable
(labeled “PC”) into the COM port on the card (see Figure 5).

Verify that you have used the port labeled “COM.” The
other ports on the card will not work for configuration.

2.

Plug the other end of the serial cable into the serial COM port
on the computer.

3.

Open your terminal emulation program (such as
HyperTerminal).

4.

Select the appropriate serial connection (such as COM1). See
Figure 6.

5.

Set the serial line to 9600 baud, No parity, 8 data bits, 1 stop
bit, and no flow control (see Figure 7).

6.

Verify that the UPS is turned on.

7.

After a few seconds, press Enter. The Password prompt
appears (see Figure 8).

If the Password prompt does not appear, press Enter again.
If it still does not appear, check the following conditions:

S

Verify the serial line is set to 9600 baud, No parity, 8 data
bits, 1 stop bit, and no flow control.

S

If the serial line settings are correct, check the cabling to
verify all connections are secure.

S

Verify that your terminal program is on the correct
communication port for the serial connection.

S

Verify that the card has power (one or more LEDs on the
card are illuminated). The UPS should be turned on.

8.

Type your 

password

 (the default is 

admin

) and press Enter.

The Main Menu screen appears.

Summary of Contents for Powerware Series

Page 1: ...Powerware Series Eaton ConnectUPS Web SNMP Card Quick Start Instructions X and BD Models...

Page 2: ...t Corporation HyperTerminal is a registered trademark of Hilgraeve Modbus is a registered trademark of Modicon IBM and AS 400 are registered trademarks of International Business Machines Inc All other...

Page 3: ...up the ConnectUPS Card in a DHCP environment the network administrator must set up the DHCP server to provide a static address each time the card makes a DHCP request Provide the network administrator...

Page 4: ...Eaton ConnectUPSt Web SNMP Card X and BD Models Quick Start Instructions 164950185Rev B www eaton com powerquality 4...

Page 5: ...ove the X Slott or BestDockt cover on the UPS rear panel Retain the screws NOTE If there is another card already installed with an attached communication cable disconnect the cable and then remove the...

Page 6: ...erTerminal 4 Select the appropriate serial connection such as COM1 See Figure 6 5 Set the serial line to 9600 baud No parity 8 data bits 1 stop bit and no flow control see Figure 7 6 Verify that the U...

Page 7: ...and 4 to set the Gateway Address and Network Mask 6 Change any other options as needed for your particular configuration by typing the corresponding number shown in the menu Each Configuration Menu se...

Page 8: ...se user guides for instructions Use the following procedure to install NetWatch software after you have installed and configured the card 1 Insert the Software Suite CD into the computer s CD ROM driv...

Page 9: ...wn your system see Figure 17 The default selection is recommended Select Next 11 The Event and Logging Options dialog opens see Figure 18 Select Next 12 Verify the configuration settings are correct a...

Page 10: ...Eaton ConnectUPSt Web SNMP Card X and BD Models Quick Start Instructions 164950185Rev B www eaton com powerquality 10...

Page 11: ......

Page 12: ...164950185B 164950185 B Eaton ConnectUPSt Web SNMP Card X and BD Models Quick Start Instructions 164950185 www eaton com powerq...

Reviews: