INTRODUCTION
EATON
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 4
www.eaton.com/powerquality
2
Providing outstanding performance and reliability, the BladeUPS module's unique
benefits include the following:
S
High-density three-phase input, three-phase output UPS.
S
Scalability to 60 kW (redundant N+1 configuration) by connecting up to five
additional parallel UPS modules. A standalone UPS converts to a parallel UPS by
changing the line cord. Each UPS in the parallel system connects to a
BladeUPS Bar pre-installed in the rear of an Eaton rack. Racks can be configured
for bottom or top entry.
A Powerware Hot Sync
®
Controller Area Network (CAN) Bridge Card in each
paralleled UPS provides connectivity for system metering and operational mode
control. In a parallel system that is not fully loaded, the system will shift load to
UPSs with the strongest batteries or additional EBMs to maximize runtime when
on battery. Parallel systems can be configured for capacity or redundancy.
S
6U height that fits any standard 48 cm (19
”
) rack.
S
Normal operating mode that minimizes heat generation by operating typically at
>96.5% efficiency. The UPS filters incoming AC power and provides consistent
power to your equipment without draining the battery.
S
For utility line input that exceeds normal operating range, automatic transfer to an
online, double-conversion, high-frequency UPS design with pure sine wave output
and power-factor correction.
S
ABM
®
technology that uses advanced battery management to increase battery
service life, optimize recharge time, and provide a warning before the end of useful
battery life.
S
Hot-swappable electronics module and batteries that simplify maintenance by
allowing you to replace them safely without powering down the critical load.
S
Emergency shutdown control through the remote emergency power-off (REPO)
port.
S
One standard communication option with a DB-9 serial port.
S
Firmware that is service upgradable through the DB-9 communication port.
S
Backed by worldwide agency approvals.
The following accessories for the BladeUPS module are available:
S
Maintenance Bypass Module (MBM) to service safely the BladeUPS module
without disrupting power.
S
EBM for extended runtime, with up to four EBMs per UPS. A 0.9m (3 ft) battery
extension cable is available.
S
X-Slot
®
cards with enhanced communication capabilities for network connectivity
with monitoring and control.
Summary of Contents for Powerware Series
Page 1: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 2: ......
Page 3: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 84: ...OPERATION EATON BladeUPS 12 kVA User s Guide S 164201649 Rev 4www eaton com powerquality 76 ...
Page 119: ......
Page 120: ... 1642016494 164201649 4 ...