UPS MAINTENANCE
EATON
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 4
www.eaton.com/powerquality
94
3.
Select CONTROL then START BATTERY TEST.
During the battery test, the front panel displays “Battery Test Pending.”
A failed battery test initiates a Battery Test Failed alarm.
To cancel a battery test in progress:
1.
Press any button to activate the menu options.
2.
Select CONTROL, START BATTERY TEST, then CANCEL.
Replacing the Electronics Module
You can easily replace the electronics module without turning the UPS off or
disconnecting the load. Battery mode is not available and your equipment is not
protected; however, the utility power continues to be filtered passively by the UPS.
If you prefer to remove input power to change the electronics module, see “Individual
UPS Shutdown” on page 72.
NOTE
DO NOT DISCONNECT the electronics module while the UPS is in Battery mode.
To replace the electronics module:
1.
Standalone UPS configurations only.
Transfer the UPS to Bypass mode. Continue to
step 3.
Parallel for capacity configurations only.
Transfer the UPS to Bypass mode. The
CAN bus remains energized.
Parallel for redundancy configurations only.
No mode transfer is necessary. If the
UPS is operating in a parallel for redundancy configuration when its electronics
module is removed, the load automatically transfers to the remaining UPSs. The
CAN bus remains energized.
NOTE
Disconnecting the control panel from the electronics module automatically transfers the UPS to
Bypass mode. However, transferring the UPS to Bypass mode manually BEFORE disconnecting the control
panel provides extra protection to the electronics module and is recommended.
2.
Parallel configurations only.
Disconnect the redundant signal cable(s) from the
UPS. For the location of the redundant signal cable, see Figure 36 on page 47.
3.
Remove the UPS front cover and the electronics module and set them aside (see
Figure 59):
To remove the UPS front cover
, grasp the fingergrips on both sides of the cover and
pull the cover forward firmly. Unplug the LCD cable connecting the back of the
control panel to the electronics module.
To remove the electronics module
, remove the electronics module locking screw at
the top left of the electronics module and retain. Grasp the ring handle at the
middle of the module and pull the module slowly out of the cabinet. Pull firmly to
unseat the connectors. Use two hands to support the module.
NOTE
Treat the electronics module with care to avoid damaging the fans, connectors, or internal circuitry.
Summary of Contents for Powerware Series
Page 1: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 2: ......
Page 3: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 84: ...OPERATION EATON BladeUPS 12 kVA User s Guide S 164201649 Rev 4www eaton com powerquality 76 ...
Page 119: ......
Page 120: ... 1642016494 164201649 4 ...