SPECIFICATIONS
EATON
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 4
www.eaton.com/powerquality
100
Table 11. BladeUPS Bar 60
Dimensions (WxDxH)
140 x 161 x 1838 mm (6.3” x 4.4” x 72.4”)
Weight
BladeUPS Bar: 19 kg (42 lb); Wireway enclosure: 20 kg (45 lb)
Total weight: 39 kg (87 lb)
UPS Connections
Up to 6, using Anderson input/output connectors
Rack Placement
Bottom wireway fits into the bottom 6U of standard rack space.
Top wireway fits into the top 6U of standard rack space.
Table 12. BladeUPS Module Rack
Dimensions (WxDxH)
610 x 1067 x 2032 mm (24” x 42” x 80”)
Weight
Rack without side panels or casters: 99 kg (219 lb);
Side panels (each): 8.5 kg (19 lb); Casters (4): 5 kg (10 lb)
Total weight: 121 kg (267 lb)
Table 13. Electrical Input
BladeUPS 12 Module
BladeUPS 12i Module
Nominal Voltage
120/208V three-phase
230/400V three-phase
Nominal Frequency
50/60 Hz
50/60 Hz
Frequency Range
45–65 Hz
45–65 Hz
Default Frequency
Auto-detected
Auto-detected
Rated Input Current
36A
24A
Connections
IEC 309-60A power cord
IEC 309-32A power cord
For paralleling, a single Anderson input/output cord connects to the
BladeUPS Bar (see Table 9 on page 99).
Noise Filtering
MOVs and common mode line filter
Input Power Factor
High Efficiency setting: load dependent
Standard setting: >0.99
Input Mode
Three-phase
Summary of Contents for Powerware Series
Page 1: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 2: ......
Page 3: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 84: ...OPERATION EATON BladeUPS 12 kVA User s Guide S 164201649 Rev 4www eaton com powerquality 76 ...
Page 119: ......
Page 120: ... 1642016494 164201649 4 ...