SPECIFICATIONS
EATON
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 4
www.eaton.com/powerquality
101
Table 14. Electrical Output
BladeUPS 12 Module
BladeUPS 12i Module
Nominal Output Voltage
120/208 Vac three-phase
230/400 Vac three-phase
Output Voltage Variation
104–132 Vac phase to neutral,
180–229 Vac phase to phase
207–253 Vac phase to neutral,
358–438 Vac phase to phase
Connections
IEC 309-60A power cord
IEC 309-32A power cord
For paralleling, a single Anderson input/output cord connects to the
BladeUPS Bar (see Table 9 on page 99).
Short Circuit Capability
(Battery Mode)
84A, <300 ms
44A, <300 ms
Short Circuit Capability
(Normal Mode)
Limited by 50A input breaker
Limited by 30A input breaker
Nominal Output Frequency
50–60 Hz auto-detection (Normal mode)
50 or 60 Hz (Battery mode)
Output Frequency Variation
Synchronized (Normal mode)
±0.1 when not synchronized with source (Battery mode)
Output Overload
100–110%: load transfers to Bypass mode after 10 minutes
110–125%: load transfers to Bypass mode after 1 minute
125–150%: load transfers to Bypass mode after 5 seconds
>150%: load transfers to Bypass mode after 300 ms
Voltage Waveform
Normal mode and Battery mode: Sine wave; <2% THD with linear load;
<5% with nonlinear load
Full Output
Three-phase
Summary of Contents for Powerware Series
Page 1: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 2: ......
Page 3: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 84: ...OPERATION EATON BladeUPS 12 kVA User s Guide S 164201649 Rev 4www eaton com powerquality 76 ...
Page 119: ......
Page 120: ... 1642016494 164201649 4 ...