Table 18. Parallel UPS System Battery Runtimes at Full/Half Load (in Minutes at Capacity)
Number of UPSs
kW
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
2
24/12
4.7/13.6
9.5/27
17/42
27/60
34/76
3
36/18
4.7/13.6
9.5/27
17/42
27/60
34/76
4
48/24
4.7/13.6
9.5/27
17/42
27/60
34/76
5
60/30
4.7/13.6
9.5/27
17/42
27/60
34/76
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.
Table 19. Parallel UPS System Battery Runtimes at Full/Half Load (in Minutes with N+1)
Number of UPSs
kW
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
2
12/6
14/30
27/56
42/89
60/128
76/165
3
24/12
8.7/23
18/42
28/66
43/94
55/120
4
36/18
7.3/20
15/37
24/57
38/82
48/105
5
48/24
6.7/19.2
13/34
23/54
35/77
44/98
6
60/30
6.2/18.4
13/33
22/52
33/74
42/94
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.