INSTALLATION
EATON
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 4
www.eaton.com/powerquality
31
Rack Setup for the UPS
C
A
U
T
I
O
N
The UPS is heavy (see page 99). Removing the UPS from its carton requires a minimum of two people. Use
the corrugated lifting sling (packaged with the UPS) to move the UPS.
NOTE
Mounting rails are required for each individual cabinet.
To install the UPS rail kit:
1.
Select the proper holes in the rack for positioning the UPS in the rack (see
Figure 17).
NOTE
The UPS takes up position 1 through position 12.
NOTE
Verify that the hole patterns on the rails and mounting brackets align with the hole pattern on the
rack.
Position 1
Position 9
Mounting
Bracket
Top of Rail
Position 12
Position 4
Bottom of Rack
or Top of Other
Cabinet
Bottom of Rail
Figure 17. Front Rail Screw Positions for the UPS