INSTALLATION
EATON
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 4
www.eaton.com/powerquality
57
UPS 3
UPS 2
UPS 1
CAN Bridge Card Cable
CAN
IN
Blue Terminating Plug
Redundant Signal Cable
For Parallel
Use Only
Standalone/
Parallel
For Parallel
Use Only
Standalone/
Parallel
Standalone/
Parallel
(remove)
CAN
OUT
Blue Terminating Plug
Figure 42. Typical CAN Bridge Card and Redundant Signal Wiring
15.
Tighten the screws securing each newly installed Powerware Hot Sync CAN
Bridge Card in its X-Slot communication bay.
16.
If you are installing power management software, connect your computer to the
UPS communication port or optional X-Slot card (see page 77). For the
communication port, use the supplied serial cable.
NOTE
You may install one ConnectUPS-X Web/SNMP Card per UPS, or one card per parallel system.
Installing one card per UPS provides communication with each UPS. Installing one card per parallel system
provides detection of a problem with at least one UPS, but does not specify which UPS or how many.
17.
If you left the UPSs unattached to the rack, secure the front and rear of each
UPS as described in Steps 14 and 15 on page 35.