Standalone UPS Initial Startup
To start up a standalone UPS:
NOTE
Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
1.
Plug the equipment to be protected into the UPS, but do not turn on the
protected equipment (see Figure 32 on page 43).
2.
Make any necessary provisions for cord retention and strain relief.
3.
Verify that all UPS circuit breakers are in the OFF (O) position.
NOTE
The load connector breaker controls the load connector only, not the output power cord.
4.
Verify that the UPS power cord is plugged in.
5.
Switch on utility power where the UPS is connected.
6.
Remove the breaker ties from the circuit breakers.
7.
Switch the UPS input circuit breaker to the ON (
) position.
8.
Wait for the UPS front panel display to illuminate.
The
indicator flashes on the UPS.
9.
Check the UPS front panel display for active alarms or notices (other than
“Batteries Disconnected”). Resolve any active alarms before continuing. See
“Troubleshooting” on page 105.
10.
Switch the UPS battery circuit breaker to the ON (
) position.
11.
If optional EBMs are installed, switch all EBM battery circuit breakers to the
ON (
) position.
12.
Verify that the “Batteries Disconnected” alarm has cleared. Verify that no other
alarms appear on the UPS front panel display.
If the
indicator is flashing, do not proceed until all alarms are clear. Check the
UPS status from the front panel to view the active alarms. Correct the alarms and
restart if necessary.
13.
Press any button on the front panel display to activate the menu options, and
then press the button until the TURN UPS ON/OFF menu displays.
14.
Press the
button to display the TURN UPS ON option; press the
button.
Summary of Contents for Powerware Series
Page 1: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 2: ......
Page 3: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 84: ...OPERATION EATON BladeUPS 12 kVA User s Guide S 164201649 Rev 4www eaton com powerquality 76 ...
Page 119: ......
Page 120: ... 1642016494 164201649 4 ...