Control Terminals
Connect the cables to the control terminals with a mating connector. Input and output
terminals have a functional isolation from terminal to terminal. They are connected to
the UPS chassis through individual 1 M
resistors.
+ Polarity
– Polarity
2
1
+ Polarity
– Polarity
2
1
2
1
2
1
Signal Input 1 (programmable)
Signal Input 2 (programmable)
REPO Normally Open
REPO Normally Closed
Normally Open
Normally Closed
1
2
Common
3
Relay Output
UPS
Connectors
(see Figure 46 on
page 77)
+ Polarity
– Polarity
2
1
Redundant Signal Wiring
(For Parallel Use Only)
+ Polarity
– Polarity
2
1
Standalone/Parallel
Figure 50. External Control Terminal Connections
NOTE
If using a semiconductor switch type, pay attention to the proper polarity. A relay or other
mechanical control is preferred.
Relay Output Contacts
The UPS incorporates a programmable relay output with potential free contacts for
remote alarm indications (see Figure 46 on page 77). You can obtain an additional four
relay outputs with the X-Slot compatible Relay Interface Card.
W
A
R
N
I
N
G
The relay output contacts must not be connected to any utility connected circuits; the utility requires
reinforced insulation. The relay output contacts have a maximum rating of 30 Vac/1A and 60 Vdc/2A nominal
values.
Summary of Contents for Powerware Series
Page 1: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 2: ......
Page 3: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 84: ...OPERATION EATON BladeUPS 12 kVA User s Guide S 164201649 Rev 4www eaton com powerquality 76 ...
Page 119: ......
Page 120: ... 1642016494 164201649 4 ...