EATON
9395 Field Installed UPM Mechanical Installation Manual
S
164201717 Rev 3
www.eaton.com/powerquality
3−1
Chapter 3
Field Installed UPM Installation Plan and Unpacking
Use the following basic sequence of steps to install the Field Installed UPM (FI−UPM):
1.
Create an installation plan for the FI−UPM (Chapter 3).
2.
Prepare your site for the FI−UPM (Chapter 3).
3.
Inspect and unpack the FI−UPM cabinet (Chapter 3).
4.
Unload and install the FI−UPM cabinet (Chapter 4).
5.
Complete the Installation Checklist (Chapter 4).
6.
Have authorized service personnel install wiring, perform preliminary operational
checks, and start up the system.
NOTE
Wiring, startup, and operational checks must be performed by an authorized Eaton Customer Service
Engineer, or the warranty terms specified on page W−1 become void. This service is offered as part of the
sales contract for the FI−UPM. Contact an Eaton service representative in advance (usually a two−week notice
is required) to request service.
3.1
Creating an Installation Plan
Before installing the FI−UPM, read and understand how this manual applies to the
system being installed. Use the procedures and illustrations in paragraph 3.2 and
Chapter 4 to create a logical plan for installing the system.
3.2
Preparing the Site
For the FI−UPM to operate at peak efficiency, the installation site should meet the
environmental parameters outlined in this manual. If the FI−UPM is to be operated at
an altitude higher than 1500m (5000 ft) for the 480V model or 1000m (3330 ft) for the
400V model , contact an Eaton service representative for important information about
high altitude operation. The operating environment must meet the weight, clearance,
and environmental requirements specified.
The FI−UPM installation must meet the following guidelines:
S
The system must be installed on a level floor suitable for computer or electronic
equipment.
S
The system must be installed in a temperature and humidity controlled indoor area
free of conductive contaminants.
S
The cabinet must be installed in
line-up-and-match
configuration.
Failure to follow guidelines may void your warranty.
Figure 3Table 3