INSTALLATION NOTES
SHEET:
REVISION:
F
164201037−1
051506
NOTE:
Callout letters
and
map to drawing #164201037−3
,
,
,
E
F
G
,
,
,
E
A
B
C
F
D
G
Customer Information
A−7
EATON
Powerware
®
9315 UPS (200–300 kVA) Installation Manual
S
164201037 Rev G
www.powerware.com
Table F. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9315 300 (0.9 pF)
Ratings
Units
Rating 60 Hz
Basic unit rating at
0.9 lagging PF load
KVA
KW
225
202.5
300
270
INPUT/OUTPUT
VOLTAGE
480
600
208
480
600
AC
INPUT
AC Input to UPS Rectifier
or Input
Transformer (
0.95min. PF)
3
O
, 1 Neutral, 1 gnd
Minimum conductor size (number per
O
)
*(Maximum amps includes full load current plus
battery recharge current)
Minimum conductor size (number per
O
)
With Filter:
Amps*
334
274
1056
450
366
AWG or kcmil(ea)
4/0(2)
500(1)
500(4)
350(2)
250(2)
Amps without Filter:
Amps*
396
323
1221
529
432
AWG or kcmil(ea)
300(2)
4/0(2)
600(4)
500(2)
350(2)
AC
INPUT
AC Input to UPS Rectifier
from Input
Transformer
3
O
, 1 Neutral, 1 gnd
Minimum conductor size (number per
O
)
*(Maximum amps includes full load current plus
battery recharge current)
Minimum conductor size (number per
O
)
Amps with Filter:
Amps*
N/A
N/A
N/A
N/A
N/A
AWG or kcmil(ea)
N/A
N/A
N/A
N/A
N/A
Amps without Filter:
Amps*
396
323
1221
529
432
AWG or kcmil(ea)
300(2)
4/0(2)
600(4)
500(2)
350(2)
AC
INPUT
AC Input to UPS Bypass
or Bypass
Transformer
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
271
217
830
360
289
AWG or kcmil(ea)
3/0(2)
350(1)
500(3)
250(2)
4/0(2)
AC
INPUT
AC Input to UPS Bypass from Bypass
Transformer
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
N/A
N/A
830
N/A
N/A
AWG or kcmil(ea)
N/A
N/A
500(3)
N/A
N/A
DC
INPUT
DC Input from Battery to UPS
(1) positive, (1) negative
Minimum conductor size (number per
O
)
VDC
Amps @ (1.8V/cell)
480
505
480
505
480
675
480
675
480
675
AWG or kcmil(ea)
4/0(3)
4/0(3)
350(3)
350(3)
350(3)
AC
OUT-
PUT
AC Output to Output Transformer or Critical
Load
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
271
217
360
360
289
AWG or kcmil(ea)
3/0(2)
350(1)
250(2)
250(2)
4/0(2)
AC
OUT-
PUT
AC Output from Output Transformer to
Critical Load
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
N/A
N/A
830
N/A
N/A
AWG or kcmil(ea)
N/A
N/A
500(3)
N/A
N/A